gutenberg.go-v.org

The filtration of public water-supplies

The Project Gutenberg eBook of The filtration of public water-supplies This eBook is for the use of anyone anywhere in the United States and most other parts of the world at no cost and with almost no restrictions whatsoever. You may copy it, give it away or re-use it under the terms of the Project Gutenberg License included with this eBook or online at www.gutenberg.org. If you are not located in the United States, you will have to check the laws of the country where you are located before using this eBook. Title: The filtration of public water-supplies Author: Allen Hazen Release date: September 21, 2022 [eBook #69025] Most recently updated: October 19, 2024 Language: English Original publication: United States: John Wiley & Sons, 1900 Other information and formats: www.gutenberg.org/ebooks/69025 Credits: Charlene Taylor, Brian G. Wilcox and the Online Distributed Proofreading Team at https://www.pgdp.net (This file was produced from images generously made available by The Internet Archive/American Libraries.) *** START OF THE PROJECT GUTENBERG EBOOK THE FILTRATION OF PUBLIC WATER-SUPPLIES *** Transcriber’s Notes: The spelling, hyphenation, punctuation and accentuation are as the original, except for apparent typographical errors which have been corrected. Italic text is denoted _thus_. Bold text is denoted =thus=. See further notes at the end of the book. [Illustration: GENERAL VIEW OF FILTERS AT HAMBURG. [_Frontispiece._] ] THE FILTRATION OF PUBLIC WATER-SUPPLIES. BY ALLEN HAZEN, MEMBER OF THE

source: Project Gutenberglicence: Public domain (per item)database: /home/dbs/gutenberg.dbmode: tablerecords: 544887 (max_rowid)citation: https://www.gutenberg.org/

The Project Gutenberg eBook of The filtration of public water-supplies

This eBook is for the use of anyone anywhere in the United States and
most other parts of the world at no cost and with almost no restrictions
whatsoever. You may copy it, give it away or re-use it under the terms
of the Project Gutenberg License included with this eBook or online
at www.gutenberg.org. If you are not located in the United States,
you will have to check the laws of the country where you are located
before using this eBook.

Title: The filtration of public water-supplies

Author: Allen Hazen

Release date: September 21, 2022 [eBook #69025]
Most recently updated: October 19, 2024

Language: English

Original publication: United States: John Wiley & Sons, 1900

Other information and formats: www.gutenberg.org/ebooks/69025

Credits: Charlene Taylor, Brian G. Wilcox and the Online Distributed Proofreading Team at https://www.pgdp.net (This file was produced from images generously made available by The Internet Archive/American Libraries.)

*** START OF THE PROJECT GUTENBERG EBOOK THE FILTRATION OF PUBLIC WATER-SUPPLIES ***

Transcriber’s Notes:

The spelling, hyphenation, punctuation and accentuation are as the
original, except for apparent typographical errors which have been
corrected.

Italic text is denoted _thus_.
Bold text is denoted =thus=.

See further notes at the end of the book.

[Illustration: GENERAL VIEW OF FILTERS AT HAMBURG.

[_Frontispiece._]
]

THE FILTRATION

OF

PUBLIC WATER-SUPPLIES.

BY
ALLEN HAZEN,

MEMBER OF THE AMERICAN SOCIETY OF CIVIL ENGINEERS, THE BOSTON SOCIETY
OF CIVIL ENGINEERS, THE AMERICAN WATER-WORKS ASSOCIATION, THE NEW
ENGLAND WATER-WORKS ASSOCIATION, THE AMERICAN CHEMICAL SOCIETY, THE
AMERICAN PUBLIC HEALTH ASSOCIATION, ETC.

_THIRD EDITION, REVISED AND ENLARGED._
SECOND THOUSAND.

NEW YORK:
JOHN WILEY & SONS.
LONDON: CHAPMAN & HALL, LIMITED.
1905.

Copyright, 1900,
BY
ALLEN HAZEN.

ROBERT DRUMMOND, ELECTROTYPER AND PRINTER, NEW YORK.

PREFACE TO FIRST EDITION.

The subject of water-filtration is commencing to receive a great deal
of attention in the United States. The more densely populated European
countries were forced to adopt filtration many years ago, to prevent
the evils arising from the unavoidable contaminations of the rivers
and lakes which were the only available sources for their public
water-supplies; and it has been found to answer its purpose so well
that at the present time cities in Europe nearly if not quite equal in
population to all the cities of the United States are supplied with
filtered water.

Many years ago, when the whole subject of water-supply was still
comparatively new in this country, filtration was considered as a means
for rendering the waters of our rivers suitable for the purpose of
domestic water-supply. St. Louis investigated this subject in 1866,
and the engineer of the St. Louis Water Board, the late Mr. J. P.
Kirkwood, made an investigation and report upon European methods of
filtration which was published in 1869, and was such a model of full
and accurate statement combined with clearly-drawn conclusions that, up
to the present time, it has remained the only treatise upon the subject
in English, notwithstanding the great advances which have been made,
particularly in the last ten years, with the aid of knowledge of the
bacteria and the germs of certain diseases in water.

Unfortunately the interest in the subject was not maintained in
America, but was allowed to lag for many years; it was cheaper to use
the water in its raw state than it was to purify it; the people became
indifferent to the danger of such use, and the disastrous epidemics
of cholera and typhoid fever, as well as of minor diseases, which so
often resulted from the use of polluted water, were attributed to other
causes. With increasing study and diffusion of knowledge the relations
of water and disease are becoming better known, and the present state
of things will not be allowed to continue; indeed at present there is
inquiry at every hand as to the methods of improving waters.

The one unfortunate feature is the question of cost. Not that the cost
of filtration is excessive or beyond the means of American communities;
in point of fact, exactly the reverse is the case; but we have been so
long accustomed to obtain drinking-water without expense other than
pumping that any cost tending to improved quality seems excessive, thus
affording a chance for the installation of inferior filters, which by
failing to produce the promised results tend to bring the whole process
into disrepute, since few people can distinguish between an adequate
filtration and a poor substitute for it. It is undoubtedly true that
improvements are made, and will continue to be made, in processes of
filtration; so it will often be possible to reduce the expense of the
process without decreasing the efficiency, but great care must be
exercised in such cases to maintain the conditions really essential to
success.

In the present volume I have endeavored to explain briefly the nature
of filtration and the conditions which, in half a century of European
practice, have been found essential for successful practice, with a
view of stimulating interest in the subject, and of preventing the
unfortunate and disappointing results which so easily result from the
construction of inferior filters. The economies which may possibly
result by the use of an inferior filtration are comparatively small,
and it is believed that in those American cities where filtration is
necessary or desirable it will be found best in every case to furnish
filters of the best construction, fully able to do what is required of
them with ease and certainty.

PREFACE TO THIRD EDITION.

There have been several distinct epochs in the development of water
purification in the United States. The first may be said to date
from Kirkwood’s report on the “Filtration of River Waters,” and the
second from the inauguration of the Lawrence Experiment Station by
the Massachusetts State Board of Health, and the construction of
the Lawrence city filter, with the demonstration of the wonderful
biological action of filters upon highly polluted waters.

The third epoch is marked by the experiments at Louisville, Pittsburg
and Cincinnati, which have greatly increased our knowledge of the
treatment of waters containing enormous quantities of suspended matter,
and have reduced to something like order the previously existing
confused mass of data regarding coagulation and rapid filtration.

The first edition of this book represented the earlier epochs
before the opening of the third. In the five years since it was
written, progress in the art of water purification has been rapid
and substantial. No apology is needed for the very complete revision
required to treat these newly investigated subjects as fully as were
other matters in the earlier editions.

In the present edition the first seven chapters remain with but few
additions. Experience has strengthened the propositions contained
in them. New data might have been added, but in few cases would the
conclusions have been altered. The remaining chapters of the book have
been entirely rewritten and enlarged to represent the added information
now available, so that the present edition is nearly twice as large as
the earlier ones. In the appendices, also, much matter has been added
relating to works in operation, particularly to those in America.

NEW YORK January, 1900.

CONTENTS.

PAGE

Chapter I. INTRODUCTION. 1
II. CONTINUOUS FILTERS AND THEIR CONSTRUCTION 5
Sedimentation-basins 8
Size of Filter-beds 10
Form of Filter-beds 11
Covers for Filters 12
III. FILTERING-MATERIALS 20
Sand 20
Sands Used in European Filters 24
Effect of Size of Grain Upon Efficiency of Filtration 30
Effect of Grain Size Upon Frequency of Scraping 32
Selection of Sand 33
Thickness of the Sand Layer 34
Underdraining 35
Gravel Layers 35
Underdrains 39
Depth of Water on Filters 45
IV. RATE OF FILTRATION AND LOSS OF HEAD 47
Effect of Rate Upon Cost of Filtration 48
Effect of Rate Upon Efficiency of Filtration 50
The Loss of Head 52
Regulation of the Rate and Loss of Head in the
Older Filters 52
Apparatus For Regulating the Rate and Loss of Head 55
Apparatus For Regulating the Rate Directly 57
Apparatus For Regulating the Height of Water Upon
Filters 59
Limit to the Loss of Head 60
V. CLEANING FILTERS 68
Frequency of Scraping 72
Quantity of Sand to Be Removed 74
Wasting the Effluents After Scraping 74
Sand-washing 76
VI. THEORY AND EFFICIENCY OF FILTRATION 83
Bacterial Examination of Waters 93
VII. INTERMITTENT FILTRATION 97
The Lawrence Filter 100
Chemnitz Water-Works 107
Application of Intermittent Filtration 111
VIII. TURBIDITY AND COLOR, AND THE EFFECT OF MUD UPON
SAND FILTERS 113
The Measurement of Color 114
Amount of Color in American Waters 115
Removal of Color 117
Measurement of Turbidity 117
Relation of Platinum-wire Turbidities to Suspended
Matters 122
Source of Turbidity 123
The Amounts of Suspended Matters in Water 129
Preliminary Processes to remove Mud 133
Effect of Mud upon Sand Filters 137
Effect of Turbidity Upon the Length of Period 137
Power of Sand Filters to Produce Clear Effluents
from Muddy Water 139
Effect of Mud Upon Bacterial Efficiency of Filters 141
Limits to the Use of Subsidence for the Preliminary
Treatment of Muddy Waters 142
IX. COAGULATION OF WATERS 144
Substances used for Coagulation 145
Coagulants Which Have Been Used 150
Amount of Coagulant required to remove Turbidity 150
Amount of Coagulant required to remove Color 153
Successive Applications of Coagulant 154
The Amount of Coagulant which Various Waters will
receive 155
X. MECHANICAL FILTERS 159
Providence Experiments 159
Louisville_Experiments 161
Lorain Tests 161
Pittsburg Experiments 162
Wasting Effluent After Washing Filters 163
Influence of Amount of Sulphate of Alumina on
Bacterial Efficiency of Mechanical Filters 165
Influence of Degree of Turbidity upon Bacterial
Efficiency of Mechanical Filters 167
Average Results Obtained with Various Quantities of
Sulphate of Alumina 171
Types of Mechanical Filters 172
Efficiency of Mechanical Filters 179
Pressure Filters 180
XI. OTHER METHODS OF FILTRATION 181
Worms Tile System 181
The Use of Asbestos 181
Filters Using High Rates of Filtration Without
Coagulants 182
Household Filters 183
XII. REMOVAL OF IRON FROM GROUND-WATERS 186
Amount of Iron Required to Render Water Objectionable 186
Cause of Iron in Ground-waters 187
Treatment of Iron-containing Waters 189
Iron-removal Plants in Operation 192
XIII. TREATMENT OF WATERS 197
Cost of Filtration 200
What Waters Require Filtration 207
XIV. WATER-SUPPLY AND DISEASE—CONCLUSIONS 210
Appendix I. RULES OF THE GERMAN GOVERNMENT IN REGARD TO THE
FILTRATION OF SURFACE-WATERS USED FOR PUBLIC
WATER-SUPPLIES 221
II. EXTRACTS FROM “BERICHT DES MEDICINAL-INSPECTORATS
DES HAMBURGISCHEN STAATES FÜR DAS JAHR 1892” 226
III. METHODS OF SAND-ANALYSIS 233
IV. FILTER STATISTICS 241
Statistics of Operation of Sand Filters 241
Partial List of Cities Using Sand Filters 244
List of Cities and Towns Using Mechanical Filters 247
Notes Regarding Sand Filters in the United States 251
Capacity of Filters 254
V. LONDON’S WATER-SUPPLY 255
VI. THE BERLIN WATER-WORKS 261
VII. ALTONA WATER-WORKS 265
VIII. HAMBURG WATER-WORKS 269
IX. NOTES ON SOME OTHER EUROPEAN WATER-SUPPLIES 272
The Use of Unfiltered Surface-waters. 275
The Use of Ground-water. 276
X. LITERATURE OF FILTRATION 277
XI. THE ALBANY WATER-FILTRATION PLANT 288
Description of Plant. 289
Capacity of Plant and Means of Regulation. 308
Results of Operation. 314
Cost of Construction. 314
INDEX 317

UNITS EMPLOYED.

The units used in this work are uniformly those in common use in
America, with the single exception of data in regard to sand-grain
sizes, which are given in millimeters. The American units were not
selected because the author prefers them or considers them particularly
well suited to filtration, but because he feared that the use of the
more convenient metric units in which the very comprehensive records
of Continental filter plants are kept would add to the difficulty of
a clear comprehension of the subject by those not familiar with those
units, and so in a measure defeat the object of the book.

TABLE OF EQUIVALENTS.

Unit. Metric Equivalent. Reciprocal.
Foot 0.3048 meter 3.2808
Mile 1609.34 meters 0.0006214
Acre 4047 square meters 0.0002471
Gallon[1] 3.785 liters 0.26417
1 million gallons 3785 cubic meters 0.00026417
Cubic yard 0.7645 cubic meters 1.308
1 million gallons per } { meter in depth }
acre daily } 0.9354 { of water daily } 1.070

ACKNOWLEDGMENT.

I wish to acknowledge my deep obligation to the large number of
European engineers, directors, and superintendents of water-works, and
to the health officers, chemists, bacteriologists, and other officials
who have kindly aided me in studying the filtration-works in their
respective cities, and who have repeatedly furnished me with valuable
information, statistics, plans, and reports.

To mention all of them would be impossible, but I wish particularly to
mention Major-General Scott, Water-examiner of London; Mr. Mansergh,
Member of the Royal Commission on the Water-supply of the Metropolis;
Mr. Bryan, Engineer of the East London Water Company; and Mr. Wilson,
Manager of the Middlesborough Water-works, who have favored me with
much valuable information.

In Holland and Belgium I am under special obligations to Messrs. Van
Hasselt and Kemna, Directors of the water companies at Amsterdam and
Antwerp respectively; to Director Stang of the Hague Water-works; to
Dr. Van’t Hoff, Superintendent of the Rotterdam filters; and to my
friend H. P. N. Halbertsma, who, as consulting engineer, has built many
of the Dutch water-works.

In Germany I must mention Profs. Frühling, at Dresden, and Flügge, at
Breslau; Andreas Meyer, City Engineer of Hamburg; and the Directors of
water-works, Beer at Berlin, Dieckmann at Magdeburg, Nau at Chemnitz,
and Jockmann at Liegnitz, as well as the Superintendent Engineers
Schroeder at Hamburg, Debusmann at Breslau, and Anklamm and Piefke at
Berlin, the latter the distinguished head of the Stralau works, the
first and most widely known upon the Continent of Europe.

I have to acknowledge my obligation to City Engineer Sechner at
Budapest, and to the Assistant Engineer in charge of water-works,
Kajlinger; to City Engineer Peters and City Chemist Bertschinger at
Zürich; and to Assistant Engineer Regnard of the Compagnie Générale des
Eaux at Paris.

On this side of the Atlantic also I am indebted to Hiram F. Mills,
C.E., under whose direction I had the privilege of conducting
for nearly five years the Lawrence experiments on filtration; to
Profs. Sedgwick and Drown for the numerous suggestions and friendly
criticisms, and to the latter for kindly reading the proof of this
volume; to Mr. G. W. Fuller for full information in regard to the
more recent Lawrence results; to Mr. H. W. Clark for the laborious
examination of the large number of samples of sands used in actual
filters and mentioned in this volume; and to Mr. Desmond FitzGerald
for unpublished information in regard to the results of his valuable
experiments on filtration at the Chestnut Hill Reservoir, Boston.

ALLEN HAZEN.

BOSTON, April, 1895.

FILTRATION OF PUBLIC WATER-SUPPLIES.

CHAPTER I.

INTRODUCTION.

The rapid and enormous development and extension of water-works in
every civilized country during the past forty years is a matter which
deserves our most careful consideration, as there is hardly a subject
which more directly affects the health and happiness of almost every
single inhabitant of all cities and large towns.

Considering the modern methods of communication, and the free exchange
of ideas between nations, it is really marvellous how each country has
met its problems of water-supply from its own resources, and often
without much regard to the methods which had been found most useful
elsewhere. England has secured a whole series of magnificent supplies
by impounding the waters of small streams in reservoirs holding enough
water to last through dry periods, while on Continental Europe such
supplies are hardly known. Germany has spent millions upon millions in
purifying turbid and polluted river-waters, while France and Austria
have striven for mountain-spring waters and have built hundreds of
miles of costly aqueducts to secure them. In the United States an
abundant supply of some liquid has too often been the objective point,
and the efforts have been most successful, the American works being
entirely unrivalled in the volumes of their supplies. I do not wish
to imply that quality has been entirely neglected in our country, for
many cities and towns have seriously and successfully studied their
problems, with the result that there are hundreds of water-supplies
in the United States which will compare favorably upon any basis with
supplies in any part of the world; but on the other hand it is equally
true that there are hundreds of other cities, including some among
the largest in the country, which supply their citizens with turbid
and unhealthy waters which cannot be regarded as anything else than a
national disgrace and a menace to our prosperity.

One can travel through England, Belgium, Holland, Germany, and large
portions of other European countries and drink the water at every city
visited without anxiety as to its effect upon his health. It has not
always been so. Formerly European capitals drank water no better than
that so often dispensed now in America. As recently as 1892 Germany’s
great commercial centre, Hamburg, having a water-supply essentially
like those of Philadelphia, Pittsburg, Cincinnati, St. Louis, New
Orleans, and a hundred other American cities, paid a penalty in one
month of eight thousand lives for its carelessness. The lesson was a
dear one, but it was not wasted. Hamburg now has a new and wholesome
supply, and other German cities the qualities of whose waters were open
to question have been forced to take active measures to better their
conditions. We also can learn something from their experience.

There are three principal methods of securing a good water-supply for a
large city. The first consists of damming a stream from an uninhabited
or but sparsely inhabited watershed, thus forming an impounding
reservoir. This method is extensively used in England and in the United
States. In the latter most of the really good and large supplies are so
obtained. It is only applicable to places having suitable watersheds
within a reasonable distance, and there are large regions where, owing
to geological and other conditions, it cannot be applied. It is most
useful in hilly and poor farming countries, as in parts of England and
Wales, in the Atlantic States, and in California. It cannot be used to
any considerable extent in level and fertile countries which are sure
to be or to become densely populated, as is the case with large parts
of France and Germany and in the Middle States.

The second method is to secure ground-water, that is, spring or well
water, which by its passage through the ground has become thoroughly
purified from any impurities which it may have contained. This was the
earliest and is the most widely used method of securing good water.
It is specially adapted to small supplies. Under favorable geological
conditions very large supplies have been obtained in this manner. In
Europe Paris, Vienna, Budapest, Munich, Cologne, Leipzig, Dresden, a
part of London, and very many smaller places are so supplied. This
method is also extensively used in the United States for small and
medium-sized places, and deserves to be most carefully studied, and
used whenever possible, but is unfortunately limited by geological
conditions and cannot be used except in a fraction of the cases where
supplies are required. No ground-water supplies yet developed in the
United States are comparable in size to those used in Europe.

The third process of securing a good water-supply is by means of
filtration of surface waters which would otherwise be unsuitable for
domestic purposes. The methods of filtration, which it is the purpose
of this volume to explain, are beyond the experimental stage; they
are now applied to the purification of the water-supplies of European
cities with an aggregate population of at least 20,000,000 people. In
the United States the use of filters is much less common, and most of
the filters in use are of comparatively recent installation.

Great interest has been shown in the subject during the last few
years, and the peculiar character of some American waters, which differ
widely in their properties from those of many European streams, has
received careful and exhaustive consideration. In Europe filtration has
been practised with continually improving methods since 1829, and the
process has steadily received wider and wider application. It has been
most searchingly investigated in its hygienic relations, and has been
repeatedly found to be a most valuable aid in reducing mortality. The
conditions under which satisfactory results can be obtained are now
tolerably well known, so that filters can be built in the United States
with the utmost confidence that the result will not be disappointing.

The cost of filtration, although considerable, is not so great as to
put it beyond the reach of American cities. It may be roughly estimated
that the cost of filtration, with all necessary interest and sinking
funds, will add 10 per cent to the average cost of water as at present
supplied.

It may be confidently expected that when the facts are better
understood and realized by the American public, we shall abandon the
present filthy and unhealthy habit of drinking polluted river and
lake waters, and shall put the quality as well as the quantity of our
supplies upon a level not exceeded by those of any country.

CHAPTER II.

CONTINUOUS FILTERS AND THEIR CONSTRUCTION.

Filtration of water consists in passing it through some substance
which retains or removes some of its impurities. In its simplest form
filtration is a straining process, and the results obtained depend upon
the fineness of the strainer, and this in turn is regulated by the
character of the water and the uses to which it is to be put. Thus in
the manufacture of paper an enormous volume of water is required free
from particles which, if they should become imbedded in the paper,
would injure its appearance or texture. Obviously for this purpose the
removal of the smaller particles separately invisible to the unaided
eye, and thus not affecting the appearance of the paper, and the
removal of which would require the use of a finer filter at increased
expense, would be a simple waste of money. When, however, a water is
to be used for a domestic water supply and transparency is an object,
the still finer particles which would not show themselves in paper, but
which are still able, in bulk, to render a water turbid, should be as
far as possible removed, thus necessitating a finer filter; and, when
there is reason to think that the water contains the germs of disease,
the filter must be fine enough to remove with certainty those organisms
so extraordinarily small that millions of them may exist in a glass of
water without imparting a visible turbidity.

It is now something over half a century since the first successful
attempts were made to filter public water-supplies, and there are
now hundreds of cities supplied with clear, healthy, filtered water.
(Appendix IV.) While the details of the filters used in different
places present considerable variations, the general form is, in
Europe at least, everywhere the same. The most important parts of a
filter are shown by the accompanying sketch, in which the dimensions
are much exaggerated. The raw water is taken from the river into a
settling-basin, where the heaviest mud is allowed to settle. In the
case of lake and pond waters the settling-tank is dispensed with, but
it is essential for turbid river-water, as otherwise the mud clogs
the filter too rapidly. The partially clarified water then passes to
the filter, which consists of a horizontal layer of rather fine sand
supported by gravel and underdrained, the whole being enclosed in a
suitable basin or tank. The water in passing through the sand leaves
behind upon the sand grains the extremely small particles which were
too fine to settle out in the settling-basin, and is quite clear as it
goes from the gravel to the drains and the pumps, which forward it to
the reservoir or city.

[Illustration: FIG. 1.—SKETCH SHOWING GENERAL ARRANGEMENT OF FILTER
PLANTS.]

The passages between the grains of sand through which the water must
pass are extremely small. If the sand grains were spherical and 1/50 of
an inch in diameter, the openings would only allow the passage of other
spheres 1/320 of an inch in diameter, and with actual irregular sands
much finer particles are held back. As a result the coarser matters
in the water are retained on the surface of the sand, where they
quickly form a layer of sediment, which itself becomes a filter much
finer than the sand alone, and which is capable of holding back under
suitable conditions even the bacteria of the passing water. The water
which passes before this takes place may be less perfectly filtered,
but even then, the filter may be so operated that nearly all of the
bacteria will be deposited in the sand and not allowed to pass through
into the effluent.

As the sediment layer increases in thickness with continued filtration,
increased pressure is required to drive the desired volume of water
through its pores, which are ever becoming smaller and reduced in
number. When the required quantity of water will no longer pass with
the maximum pressure allowed, it is necessary to remove, by scraping,
the sediment layer, which should not be more than an inch deep. This
layer contains most of the sediment, and the remaining sand will then
act almost as new sand would do. The sand removed may be washed for use
again, and eventually replaced when the sand layer becomes too thin
by repeated scrapings. These operations require that the filter shall
be temporarily out of use, and as water must in general be supplied
without intermission, a number of filters are built together, so that
any of them can be shut out without interfering with the action of the
others.

The arrangement of filters in relation to the pumps varies with local
conditions. With gravity supplies the filters are usually located below
the storage reservoir, and, properly placed, involve only a few feet
loss of head.

In the case of tidal rivers, as at Antwerp and Rotterdam, the quality
of the raw water varies with the tide, and there is a great advantage
in having the settling-basins low enough so that a whole day’s supply
can be rapidly let in when the water is at its best, without pumping.
At Antwerp the filters are higher, and the water is pumped from the
settling basins to them, and again from the reservoir receiving the
effluents from the filters to the city. In several of the London
works (East London, Grand Junction, Southwark and Vauxhall, etc.) the
settling-basins are lower than the river, and the filters are still
lower, so that a single pumping suffices, that coming between the
filter and the city, or elevated distributing reservoir.

In many other English filters and in most German works the
settling-basins and filters are placed together a little higher than
the river, thus avoiding at once trouble from floods and cost for
excavation. The water requires to be pumped twice, once before and once
after filtration. At Altona the settling-basins and filters are placed
upon a hill, to which the raw Elbe water is pumped, and from which it
is supplied to the city after filtration by gravity without further
pumping. The location of the works in this case is said to have been
determined by the location of a bed of sand suitable for filtration on
the spot where the filters were built.

When two pumpings are required they are frequently done, especially in
the smaller places, in the same pumping-station, with but one set of
boilers and engines, the two pumps being connected to the same engine.
The cost is said to be only slightly greater than that of a single
lift of the same total height. In very large works, as at Berlin and
Hamburg and some of the London companies, two separate sets of pumping
machinery involve less extra cost relatively than would be the case
with smaller works.

SEDIMENTATION-BASINS.

Kirkwood[2] found in 1866 that sedimentation-basins were essential
to the successful treatment of turbid river-waters, and subsequent
experience has not in any way shaken his conclusion. The German works
visited by him, Berlin (Stralau) and Altona, were both built by English
engineers, and their settling-basins did not differ materially from
those of corresponding works in England. Since that time, however,
there has been a well-marked tendency on the part of the German
engineers to use smaller, while the English engineers have used much
larger sedimentation-basins, so that the practices of the two countries
are now widely separated, the difference no doubt being in part at
least due to local causes.

Kirkwood found sedimentation-basins at Altona with a capacity of
2-1/4 times the daily supply. In 1894 the same basins were in use,
although the filtering area had been increased from 0.82 acre to 2.20
acres, and still more filters were in course of construction, and
the average daily quantity of water had increased from 600,000 to
4,150,000 gallons in 1891-2, or more than three times the capacity of
the sedimentation-basins. In 1890 the depth of mud deposited in these
basins was reported to be two feet deep in three months. At Stralau in
Berlin, also, in the same time the filtering area was nearly doubled
without increasing the size of the sedimentation-basins, but the Spree
at this point has such a slow current that it forms itself a natural
sedimentation-basin. At Magdeburg on the Elbe works were built in 1876
with a filtering area of 1.92 acres, and a sedimentation-basin capacity
of 11,300,000 gallons, but in 1894 half of the latter had been built
over into filters, which with two other filters gave a total filtering
surface of 3.90 acres, with a sedimentation-basin capacity of only
5,650,000 gallons. The daily quantity of water pumped for 1891-2 was
5,000,000 gallons, so that the present sedimentation-basin capacity is
about equal to one day’s supply, or relatively less than a third of the
original provision. The idea followed is that most of the particles
which will settle at all will do so within twenty-four hours, and that
a greater storage capacity may allow the growth of algæ, and that the
water may deteriorate rather than improve in larger tanks.

[Illustration: PAVED EMBANKMENT BETWEEN TWO FILTERS, EAST LONDON.]

[Illustration: FILTERS AND CHANNELS FOR RAW WATER, ANTWERP.]

[_To face page 10._]

At London, on the other hand, the authorities consider a large storage
capacity for unfiltered water as one of the most important conditions
of successful filtration, the object however, being perhaps as much to
secure storage as to allow sedimentation. In 1893 thirty-nine places
were reported upon the Thames and the Lea which were giving their
sewage systematic treatment before discharging it into the streams
from which London’s water is drawn. These sewage treatments are, with
hardly an exception, dry-weather treatments, and as soon as there is
a considerable storm crude sewage is discharged into the rivers at
every point. The rivers are both short, and are quickly flooded, and
afterwards are soon back in their usual condition. At these times of
flood, the raw water is both very turbid and more polluted by sewage
than at other times, and it is the aim of the authorities to have the
water companies provide reservoir capacity enough to carry them through
times of flood without drawing any water whatever from the rivers. This
obviously involves much more extensive reservoirs than those used in
Germany, and the companies actually have large basins and are still
adding to them. The storage capacities of the various companies vary
from 3 to 18 times the respective average daily supplies, and together
equal 9 times the total supply.

In case the raw water is taken from a lake or a river at a point where
there is but little current, as in a natural or artificial pond,
sedimentation-basins are unnecessary. This is the case at Zürich (lake
water), at Berlin when the rivers Havel and Spree spread into lakes, at
Tegel and Müggel, and at numerous other works.

SIZE OF FILTER-BEDS.

The total area of filters required in any case is calculated from the
quantity of water required, the rate of filtration, and an allowance
for filters out of use while being cleaned. To prevent interruptions
of the supply at times of cleaning, the filtering area is divided into
beds which are operated separately, the number and size of the beds
depending upon local conditions. The cost per acre is decreased with
large beds on account of there being less wall or embankment required,
while, on the other hand, the convenience of operation may suffer,
especially in small works. It is also frequently urged that with large
filters it is difficult or impossible to get an even rate of filtration
over the entire area owing to the frictional resistance of the
underdrains for the more distant parts of the filter. A discussion of
this point is given in Chapter III, page 41. At Hamburg, where the size
of the single beds, 1.88 acres each, is larger than at any other place,
it is shown that there is no serious cause for anxiety; and even if
there were, the objectionable resistance could be still farther reduced
by a few changes in the under-drains. The sizes of filter-beds used at
a large number of places are given in Appendix IV.

At a number of places having severe winters, filters are vaulted over
as a protection from cold, and in the most important of these, Berlin,
Warsaw, and St. Petersburg, the areas of the single beds are nearly
the same, namely, from 0.52 to 0.59 acre. The works with open filters
at London (seven companies), Amsterdam, and Breslau have filter-beds
from 0.82 to 1.50 acres each. Liverpool and Hamburg alone use filters
with somewhat larger areas. Large numbers of works with both covered
and open filters have much smaller beds than these sizes, but generally
this is to avoid too small a number of divisions in a small total area,
although such works have sometimes been extended with the growth of the
cities until they now have a considerable number of very small basins.

FORM OF FILTER-BEDS.

The form and construction of the filter-beds depend upon local
conditions, the foundations, and building materials available, the
principles governing these points being in general the same as for the
construction of ordinary reservoirs. The bottoms require to be made
water-tight, either by a thin layer of concrete or by a pavement upon
a puddle layer. For the sides either masonry walls or embankments are
used, the former saving space, but being in general more expensive in
construction. Embankments must, of course, be substantially paved near
the water-line to withstand the action of ice, and must not be injured
by rapid fluctuations in the water-levels in the filters.

Failure to make the bottoms water-tight has perhaps caused more
annoyance than any other single point. With a leaky bottom there
is either a loss of water when the water in the filters is higher
than the ground-water, or under reverse conditions, the ground-water
comes in and mixes with the filtered water, and the latter is rarely
improved and may be seriously damaged by the admixture. And with very
bad conditions water may pass from one filter to another, with the
differences in pressure always existing in neighboring filters, with
most unsatisfactory results.

COVERS FOR FILTERS.

The filters in England and Holland are built open, without protection
from the weather. In Germany the filters first built were also open,
but in the colder climates more or less difficulty was experienced
in keeping the filters in operation in cold weather. An addition to
the Berlin filters, built in 1874, was covered with masonry vaulting,
over which several feet of earth were placed, affording a complete
protection against frost. The filters at Magdeburg built two years
later were covered in the same way, and since that time covered filters
have been built at perhaps a dozen different places.

[Illustration: INTERIOR VIEW OF COVERED FILTER, ASHLAND, WIS.

When in use the water rises nearly to the springing line of the arches.]

[Illustration: COVERED FILTER IN COURSE OF CONSTRUCTION, SHOWING WOODEN
CENTERS FOR MASONRY VAULTING, SOMERSWORTH, N. H.]

[_To face page 12._]

It was found at Berlin that, owing to the difficulty of properly
cleaning the open filters in winter, it was impossible to keep the
usual proportion of the area in effective service, and as a result
portions of the filters were greatly overtaxed during prolonged
periods of cold weather. This resulted in greatly decreased bacterial
efficiency, the bacteria in March, 1889, reaching 3000 to 4000 per
cc. (with 100,000 in the raw water), although ordinarily the effluent
contained less than 100. An epidemic of typhoid fever followed, and was
confined to that part of the city supplied from the Stralau works,
the wards supplied from the covered Tegel filters remaining free from
fever. Open filters have since been abandoned in Berlin.

At Altona also, where the water is taken from an excessively polluted
source, decreased bacterial efficiency has repeatedly resulted in
winter, and the occasional epidemics of typhoid fever in that city,
which have invariably come in winter, appear to have been directly due
to the effect of cold upon the open filters. The city has just extended
the open filters, and hopes with an increased reserve area to avoid
the difficulty in future without resource to covered filters. (See
Appendices II and VII.)

Brunswick, Lübeck, and Frankfort on Oder with cold winters have open
filters, but draw their water-supplies from less polluted sources, and
have thus far escaped the fate of Berlin and Altona. The new filters
at Hamburg also are open. At Zürich, where open and covered filters
were long used side by side, the covered filters were much more
satisfactory, and the old open filters have recently been vaulted over.

Königsberg originally built open filters, but was afterward obliged to
cover them, on account of the severe winters; and at Breslau, where
open filters have long been used, the recent additions are vaulted over.

The fact that inferior efficiency of filtration results with open
filters during prolonged and severe winter weather is generally
admitted, although there is some doubt as to the exact way in which
the disturbance is caused. In some works I am informed that in cutting
the ice around the edges of the filter and repeatedly piling the
loose pieces upon the floating cake, the latter eventually becomes so
thickened at the sides that the projecting lower corners actually touch
the sand, with the fluctuating levels which often prevail in these
works, and that in this way the sediment layer upon the top of the sand
is broken and the water rapidly passes without adequate purification at
the points of disturbance.

This theory is, however, inadequate to account for many cases where
such an accumulation of ice is not allowed. In these cases the poor
work is not obtained until after the filters have been scraped. The
sand apparently freezes slightly while the water is off, and when water
is brought back and filtration resumed, normal results are for some
reason not again obtained for a time.

In addition to the poorer work from open filters in cold weather, the
cost of removing the ice adds materially to the operating expenses, and
in very cold climates would in itself make covers advisable.

I have arranged the European filter plants, in regard to which I have
sufficient information, in the table on page 15, in the order of the
normal mean January temperatures of the respective places. This may not
be an ideal criterion of the necessity of covering filters, but it is
at least approximate, and in the absence of more detailed comparisons
it will serve to give a good general idea of the case. I have not
found a single case where covered filters are used where the January
temperature is 32° F. or above. In some of these places some trouble is
experienced in unusually cold weather, but I have not heard of any very
serious difficulty or of any talk of covering filters at these places
except at Rotterdam, where a project for covering was being discussed.

Those places having January temperatures below 30° experience a great
deal of difficulty with open filters; so much so, that covered filters
may be regarded as necessary for them, although it is possible to keep
open filters running with decreased efficiency and increased expense by
freely removing the ice, with January temperatures some degrees lower.

Where the mean January temperature is 30° to 32° F. there is room for
doubt as to the necessity of covering filters, but, judging from the
experience of Berlin and Altona, the covered filters are much safer at
this temperature.

TABLE OF PLACES HAVING OPEN AND COVERED FILTERS.

ARRANGED ACCORDING TO THE MEAN JANUARY TEMPERATURES.

------------+------------------+--------------------------------------
Normal Mean | |
January | Place. | Kind of Filters and Results.
Temperature.| |
Degrees F. | |
------------+------------------+--------------------------------------
37-40° |All English cities|Open filters only are used, and no
| | great difficulty with ice is
| | experienced.
33-35° |Cities in Holland |All filters are open, and there is
| | little serious trouble with ice;
| | but at Amsterdam and Rotterdam
| | the bacteria in effluents are said
| | to be higher in winter than at
| | other times.
32° | Bremen |Open filters.
31° | Altona |Much difficulty with ice in open
| | filters (see Appendices II and VII).
31° | Brunswick |Open filters.
31° | Hamburg |Open filters.
31° | Lübeck |Open filters.
31° | Berlin |Open filters were formerly used, but
| | owing to decreased efficiency in
| | cold weather they have been
| | abandoned for covered ones.
31° | Magdeburg |Covered filters, but a recent addition
| | is not covered.
30° |Frankfort on Oder |Open filters.
30° | Stuttgart |Part of the filters are covered.
30° | Stettin |Part of the filters are covered.
29° | Zürich |Covered filters were much the most
| | satisfactory, and the open ones were
| | covered in 1894. The raw water has a
| | temperature of 35°.
29° | Liegnitz |Open filters.
29° | Breslau |Open filters have been used, but
| | recent additions are covered.
29° | Budapest |Covered filters only.
29° | Posen |Covered filters only.
26° | Königsberg |The original filters were open, but it
| | was found necessary to cover them.
24° | Warsaw |Covered filters only.
16° | St. Petersburg |Covered filters only.
------------+------------------+--------------------------------------

In case the raw water was drawn from a lake at a depth where its
minimum temperature was above 32°, which is the temperature which must
ordinarily be expected in surface-waters in winter, open filters might
be successfully used in slightly colder places.

The covers are usually of brick or concrete vaulting supported by
pillars at distances of 11 to 15 feet in each direction, the whole
being covered by 2 or 3 feet of earth; and the top can be laid out as
a garden if desired. Small holes for the admission of air and light
are usually left at intervals. The thickness of the masonry and the
sizes of the pillars used in some of the earlier German vaultings are
unnecessarily great, and some of the newer works are much lighter. For
American use, vaulting like that used for the Newton, Mass., covered
reservoir[3] should be amply strong.

Roofs have been used at Königsberg, Posen, and Budapest instead of
the masonry vaulting. They are cheaper, but do not afford as good
protection against frost, and even with great care some ice will form
under them.

Provision must be made for entering the filters freely to introduce and
remove sand. This is usually accomplished by raising one section of
vaulting and building a permanent incline under it from the sand line
to a door above the high-water line in the filter.

The cost of building covered filters is said to average fully one half
more than open filters.

Among the incidental advantages of covered filters is that with the
comparative darkness there is no tendency to algæ growths on the
filters in summer, and the frequency of scraping is therefore somewhat
reduced. At Zürich, in 1892, where both covered and open filters were
in use side by side, the periods between scrapings averaged a third
longer in the covered than in the open filters.

It has been supposed that covered filters kept the water cool in summer
and warm in winter, but owing to the large volume of water passing, the
change in temperature in any case is very slight; Frühling found that
even in extreme cases a change of over 3° F. in either direction is
rarely observed.

[Illustration: REMOVING ICE FROM A FILTER, EAST LONDON.

This represents the greatest accumulation of ice in the history of the
works.

[_To face page 16._]]

At Berlin, where open and covered filters were used side by side at
Stralau for twenty years, it was found that, bacterially, the open
filters were, except in severe winter weather, more efficient. It was
long supposed that this was caused by the sterilizing action of the
sunlight upon the water in the open filters. This result, however, was
not confirmed elsewhere, and it was finally discovered, in 1893, that
the higher numbers were due to the existence of passages in corners
on the columns of the vaulted roof and around the ventilators for the
underdrains, through which, practically, unfiltered water found its
way into the effluent. This at once removes the evidence in favor of
the superior bacterial efficiency of open filters and suggests the
necessity of preventing such passages. The construction of a ledge all
around the walls and pillars four inches wide and a little above the
gravel, as shown in the sketch, might be useful in this way, and the
slight lateral movement of the water in the sand above would be of no
consequence. The sand would evidently make a closer joint with the
horizontal ledge than with the vertical wall.

[Illustration: FIG. 2.]

In regard to the probable requirement or advisability of covers for
filters in the United States, I judge, from the European experience,
that places having January temperatures below the freezing-point will
have considerable trouble from open filters, and would best have
covered filters. Places having higher winter temperatures will be
able to get along with the ice which may form on open filters, and
the construction of covers would hardly be advisable except under
exceptional local conditions, as, for instance, with a water with an
unusual tendency to algæ growths.

I have drawn a line across a map of the United States on this basis
(shown by the accompanying plate) and it would appear that places far
north of the line would require covered filters, and that those south
of it would not, while for the places in the immediate vicinity of the
line (comparable to Hamburg and Altona) there is room for discussion.

In the United States covered filters have been constructed at St.
Johnsbury, Vt., Somersworth, N. H., Albany, N. Y., Ashland, Wis., and
Grand Forks, N. Dak., all of these places being considerably north of
the above-mentioned line.

The filter at Lawrence, Mass., with a mean January temperature of
about 25°, is not covered, but serious difficulty and expense have
been experienced at times from the ice, so much so that it has been
repeatedly recommended to cover it. Open filters have also been in use
for many years at Hudson and Poughkeepsie, N. Y., with mean January
temperatures about 24°; and although considerable difficulty has been
experienced from ice at times, these filters, particularly the ones
at Poughkeepsie, have been kept in very serviceable condition at all
times, notwithstanding the ice.

At Mount Vernon, N. Y., with a mean January temperature of about
31°, and with a reservoir water, no serious difficulty has been
experienced with ice; and at Far Rockaway, L. I., with a slightly
higher temperature and well-water, no difficulty whatever has been
experienced with open filters. Filters at Ilion, N. Y., with a mean
January temperature of about 23°, are not covered, and are fed from a
reservoir. No serious difficulty has been experienced with ice, which
is probably due to the fact that the water applied to them is taken
from near the bottom of the reservoir, and ordinarily has a temperature
somewhat above the freezing-point throughout the winter.

[Illustration: Map showing

Normal Mean January Temperatures

IN THE UNITED STATES

and the Area in which Filters should be covered]

The cost of removing ice from filters depends, among other things,
upon the amount of reserve filter area. When this reserve is small
the filters must be kept constantly at work nearly up to their rated
capacity; the ice must be removed promptly whenever the filters
require cleaning, and under some conditions the expense of doing this
may be considerable. If, on the other hand, there is a considerable
reserve area, so that when a filter becomes clogged in severe weather,
the work can be turned upon other filters and the clogged filter
allowed to remain until more moderate weather, or until a thaw, the
expense of ice removal may be kept at a materially lower figure.

In case open filters are built near or north of this line, I would
suggest that plenty of space between and around the filters for piling
up ice in case of necessity may be found advantageous, and that a
greater reserve of filtering area for use in emergencies should be
provided than would be considered necessary with vaulted filters or
with open filters in a warmer climate.

CHAPTER III.

FILTERING MATERIALS.

SAND.

The sand used for filtration may be obtained from the sea-shore, from
river-beds or from sand-banks. It consists mainly of sharp quartz
grains, but may also contain hard silicates. As it occurs in nature it
is frequently mixed with clayey or other fine particles, which must be
removed from it by washing before it is used. Some of the New England
sands, however, as that used for the Lawrence City filter, are so clean
that washing would be superfluous.

The grain size of the sand best adapted to filtration has been
variously stated at from 1/8 to 1 mm., or from 0.013 to 0.040 inch.
The variations in the figures, however, are due more to the way that
the same sand appears to different observers than to actual variations
in the size of sands used, which are but a small fraction of those
indicated by these figures.

As a result of experiments made at the Lawrence Experiment Station[4]
we have a standard by which we can definitely compare various sands.
The size of a sand-grain is uniformly taken as the diameter of a sphere
of equal volume, regardless of its shape. As a result of numerous
measurements of grains of Lawrence sands, it is found that when the
diameter, as given above, is 1, the three axes of the grain, selecting
the longest possible and taking the other two at right angles to it,
are, on an average, 1.38, 1.05, and 0.69, respectively and the mean
diameter is equal to the cube root of their product.

It was also found that in mixed materials containing particles of
various sizes the water is forced to go around the larger particles and
through the finer portions which occupy the intervening spaces, so that
it is the finest portion which mainly determines the character of the
sand for filtration. As a provisional basis which best accounts for the
known facts, the size of grain such that 10 per cent by weight of the
particles are smaller and 90 per cent larger than itself, is considered
to be the _effective size_. The size so calculated is uniformly
referred to in speaking of the size of grain in this work.

[Illustration: FIG. 3.—APPARATUS USED FOR MEASURING THE FRICTION OF
WATER IN SANDS.]

Another important point in regard to a material is its degree of
uniformity—whether the particles are mainly of the same size or whether
there is a great range in their diameters. This is shown by the
_uniformity coefficient_, a term used to designate the ratio of the
size of the grain which has 60 per cent of the sample finer than itself
to the size which has 10 per cent finer than itself.

The frictional resistance of sand to water when closely packed, with
the pores completely filled with water and in the entire absence of
clogging, was found to be expressed by the formula

_v_ = _cd_^2(_h_/_l_)(_t_ Fah. + 10°)/60,

where _v_ is the velocity of the water in meters daily in a solid column
of the same area as that of the sand, or approximately in
million gallons per acre daily;
_c_ is an approximately constant factor;
_d_ is the effective size of sand grain in millimeters;
_h_ is the loss of head (Fig. 3);
_l_ is the thickness of sand through which the water passes;
_t_ is the temperature (Fahr.).

TABLE SHOWING RATE AT WHICH WATER WILL PASS THROUGH EVEN-GRAINED AND
CLEAN SANDS OF THE STATED GRAIN SIZES AND WITH VARIOUS HEADS AT A
TEMPERATURE OF 50°.

-------+--------------------------------------------------------------
| Effective Size in Millimeters 10 per cent finer than:
_h_/_l_+------+------+-------+--------+--------+--------+-------+-----
| 0.10 | 0.20 | 0.30 | 0.35 | 0.40 | 0.50 | 1.00 | 3.00
-------+------+------+-------+--------+--------+--------+-------+-----
| | | Million Gallons per Acre daily. | |
.001 | .01 | .04 | .10 | .13 | .17 | .27 | 1.07 | 9.63
.005 | .05 | .21 | .48 | .65 | .85 | 1.34 | 5.35 |48.15
.010 | .11 | .43 | .96 | 1.31 | 1.71 | 2.67 | 10.70 |96.30
.050 | .54 | 2.14 | 4.82 | 6.55 | 8.55 | 13.40 | 53.50 |
.100 | 1.07 | 4.28 | 9.63 | 13.10 | 17.10 | 26.70 |107.00 |
1.000 |10.70 |42.80 | 96.30 | 131.00 | 171.00 | 267.00 | |
-------+------+------+-------+--------+--------+--------+-------+-----

The above table is computed with the value _c_ taken as 1000, this
being approximately the values deduced from the earliest experiments.
More recent and extended data have shown that the value of _c_ is not
entirely constant, but depends upon the uniformity coefficient, upon
the shape of the sand grains, upon their chemical composition, and upon
the cleanliness and closeness of packing of the sand. The value may be
as high as 1200 for very uniform, and perfectly clean sand, and maybe
as low as 400 for very closely packed sands containing a good deal
of alumina or iron, and especially if they are not quite clean. The
friction is usually less in new sand than in sand which has been in use
for some years. In making computations of the frictional resistance
of filters, the average value of _c_ may be taken at from 700 to 1000
for new sand, and from 500 to 700 for sand which has been in use for a
number of years.

The value of _c_ decreases as the uniformity coefficient increases.
With ordinary filter sands with uniformity coefficients of 3 or less
the differences are not great. With mixed sands having much higher
uniformity coefficients, lower and less constant values of _c_ are
obtained, and the arrangement of the particles becomes a controlling
factor in the increase in friction.

The friction of the surface layer of a filter is often greater than
that of all the sand below the surface. It must be separately computed
and added to the resistances computed by the formula, as it depends
largely upon other conditions than those controlling the resistance of
the sand.

While the value of _c_ is thus not entirely constant, it can be
estimated with approximate accuracy for various conditions, from a
knowledge of the composition, condition, and cleanliness of the sand,
and closeness of packing.

The following table shows the quantity of water passing sands at
different temperatures. This table was computed with temperature
factors as given above, which were based upon experiments upon the
flow of water through sands, checked by the coefficients obtained from
experiments with long capillary tubes entirely submerged in water of
the required temperature.

RELATIVE QUANTITIES OF WATER PASSING AT DIFFERENT TEMPERATURES.

32° 0.70
35° 0.75
38° 0.80
41° 0.85
44° 0.90
47° 0.95
50° 1.00
53° 1.05
56° 1.10
59° 1.15
62° 1.20
65° 1.25
68° 1.30
71° 1.35
74° 1.40
77° 1.45

The effect of temperature upon the passage of water through sands and
soils has been further discussed by Prof. L. G. Carpenter, _Engineering
News_, Vol. XXXIX, p. 422. This article reviews briefly the literature
of the subject, and refers at length to the formula of Poiseuille,
published in the _Memoires des Savants Etrangers_, Vol. XI, p. 433
(1846). This formula, in which the quantity of water passing at 0.0°
Cent., is taken as unity, is as follows:

Temperature factor = 1 + 0.033679_t_ + 0.000221_t_^2.

The results obtained by this formula agree very closely with those
given in the above table throughout the temperature range for
which computations are most frequently required. At the higher and
lower temperatures the divergencies are greater, as is shown in a
communication in the _Engineering News_, Vol. XL, p. 26.

The quantity of water passing at a temperature of 50° Fahr. is in many
respects more convenient as a standard than the quantity passing at the
freezing-point. Near the freezing-point, owing to molecular changes in
the water, the changes in its action are rapid, and the results are
less certain, and also 50° Fahr. is a much more convenient temperature
for precise experiments than is the freezing point.

SANDS USED IN EUROPEAN FILTERS.

To secure definite information in regard to the qualities of the sands
actually used in filtration, a large number of European works were
visited in 1894, and samples of sand were collected for analysis. These
samples were examined at the Lawrence Experiment Station by Mr. H. W.
Clark, the author’s method of analysis described in Appendix III being
used. In the following table, for the sake of compactness, only the
leading points of the analyses, namely, effective size, uniformity
coefficient, and albuminoid ammonia, are given. On page 28 full
analyses of some samples from a few of the leading works are given.

ANALYSES OF SANDS USED IN WATER FILTRATION.

---------------------+---------+--------+--------+--------------------
|Effective| | Albu- |
|Size; 10%| Uni- | minoid |
| Finer |formity | Ammo- |
Source. | than | Coeffi-| nia. | Remarks.
|(Milli- | cient. |Parts in|
| meters).| |100,000.|
---------------------+---------+--------+--------+--------------------
London, E. London Co.| 0.44 | 1.8 | 0.45 |New sand, never
| | | | used or washed.
London, E. London Co.| 0.39 | 2.1 | 26.20 |Dirty sand, very
| | | | old.
London, E. London Co.| 0.37 | 2.0 | 8.60 |Same, washed by
| | | | hand.
London, Grand Junc. | 0.26 | 1.9 | 1.90 |Sand from rough
| | filter.
London, Grand Junc. | 0.40 | 3.5 | 10.00 |Old sand in final
| | | | filter.
London, Grand Junc. | 0.41 | 3.7 | 2.70 |Freshly washed old
| | | | sand.
London, Southw’k & V.| 0.38 | 3.5 | 5.00 |Freshly washed old
| | | | sand.
London, Southw’k & V.| 0.30 | 1.8 | 2.80 |Freshly washed new
| | | | sand.
London, Lambeth | 0.36 | 2.3 | 2.60 |Freshly washed old
| | | | sand.
London, Lambeth | 0.36 | 2.4 | 0.35 |New unused sand,
| | | washed.
London, Lambeth | 0.25 | 1.7 | 0.70 |New extremely fine
| | | | sand.
London, Chelsea | 0.36 | 2.4 | 2.10 |Freshly washed old
| | | | sand.
Middlesborough | 0.42 | 1.6 | 17.60 |Dirty sand, ordinary
| | | | scraping.
Middlesborough | 0.43 | 1.6 | 7.30 |Same, after washing.
Birmingham | 0.29 | 1.9 | 33.20 |Dirty sand.
Birmingham | 0.29 | 1.9 | 7.20 |Sand below surface
| | | | of filter.
Reading | 0.30 | 2.5 | 4.00 |Dirty sand.
Reading | 0.22 | 2.0 | 1.50 |Same, after washing.
Antwerp | 0.38 | 1.6 | 7.80 |Dirty sand.
Antwerp | 0.39 | 1.6 | 3.40 |Same, after washing.
Hamburg | 0.28 | 2.5 | 8.50 |Dirty sand.
Hamburg | 0.31 | 2.3 | 0.80 |Same, after washing.
Hamburg | 0.34 | 2.2 | 7.90 |Dirty sand, another
| | | | sample.
Hamburg | 0.30 | 2.0 | 0.90 |Same, after washing
| | | | drums.
Hamburg | 0.34 | 2.3 | 1.50 |Same, after washing
| | | | ejectors.
Altona | 0.32 | 2.0 | 9.00 |Dirty sand, old
| | | | filters.
Altona | 0.37 | 2.0 | 1.50 |Same, after washing.
Altona | 0.33 | 2.8 | 0.50 |Washed sand for new
| | | | filters.
Berlin, Stralau | 0.33 | 1.9 | 12.20 |Dirty sand-pile.
Berlin, Stralau | 0.35 | 1.7 | 4.50 |Filter No. 6,
| | | | 3″ below surface.
Berlin, Stralau | 0.34 | 1.7 | 6.30 |Filter No. 7,
| | | | 3″ below surface.
Berlin, Stralau | 0.35 | 1.7 | 4.00 |Filter No. 10,
| | | | 3″ below surface.
Berlin, Tegel | 0.38 | 1.6 | 11.00 |Dirty sand, old
| | | | filters.
Berlin, Tegel | 0.38 | 1.5 | 2.80 |Same, after washing,
| | | | old filters.
Berlin, Tegel | 0.35 | 1.6 | 3.20 |Same, after washing,
| | | | new filters.
Berlin, Müggel | 0.35 | 1.8 | 0.80 |Sand from filters
| | | | below surface.
Berlin, Müggel | 0.33 | 2.0 | 6.30 |Dirty sand, ordinary
| | | | scraping.
Berlin, Müggel | 0.34 | 2.0 | 15.30 |Dirty sand, another
| | | | sample.
Charlottenburg | 0.40 | 2.3 | 7.20 |Dirty sand.
Chemnitz | 0.35 | 2.6 | 0.20 |New sand not yet
| | | | used.
Magdeburg | 0.39 | 2.0 | 9.50 |Dirty sand.
Magdeburg | 0.40 | 2.0 | 2.80 |Same, after washing.
Breslau | 0.39 | 1.8 | 1.40 |Normal new sand.
Budapest | 0.20 | 2.0 | 0.80 |New washed Danube
| | | | sand.
Zürich | 0.28 | 3.2 | 6.20 |Dirty sand.
Zürich | 0.30 | 3.1 | 1.50 |Same, after washing.
Hague | 0.19 | 1.6 | 0.70 |Dune-sand used for
| | | | filtration.
Schiedam | 0.18 | 1.6 | 5.60 |Dune-sand used for
| | | | filtration; dirty.
Schiedam | 0.31 | 1.5 | 13.50 |River-sand; dirty.
Amsterdam | 0.17 | 1.6 | 2.40 |Dune-sand.
Rotterdam | 0.34 | 1.5 | 2.30 |River-sand; new.
Liverpool, Rivington | 0.43 | 2.0 | 0.76 |Sand from bottom of
| | | | filter.
Liverpool, Rivington | 0.32 | 2.5 | 1.00 |New sand unwashed
| | | | and unscreened.
Liverpool, Rivington | 0.43 | 2.7 | 4.10 |Washed sand which
| | | | has been in use
| | | | 30 to 40 years.
Liverpool, Oswestry | 0.30 | 2.6 | 9.40 |Dirty sand.
Liverpool, Oswestry | 0.31 | 4.7 | 2.20 |Same, after washing.
---------------------+---------+--------+--------+--------------------

NOTE.—It is obvious that in case the sands used at any place are not
always of the same character, as is shown to be the case by different
samples from some of the works, the examination of such a limited
number of samples as the above from each place is entirely inadequate
to establish accurately the sizes of sand used at that particular
place, or to allow close comparisons between the different works, and
for this reason no such comparisons will be made. The object of these
investigations was to determine the sizes of the sands commonly used
in Europe, and, considering the number and character of the different
works represented, it is believed that the results are ample for this
purpose.

The English and most of the German sands are washed, even when entirely
new, before being used, to remove fine particles. At Breslau, however,
sand dredged from the river Oder is used in its natural state, and
new sand is used for replacing that removed by scraping. At Budapest,
Danube sand is used in the same way, but with a very crude washing, and
it is said that only new unwashed sand is used at Warsaw.

In Holland, so far as I learned, no sand is washed, but new sand is
always used for refilling. At most of the works visited dune-sand
with an effective size of only 0.17 to 0.19 mm. is used, and this is
the finest sand which I have ever found used for water filtration on
a large scale. It should be said, however, that the waters filtered
through these fine sands are fairly clear before filtration, and are
not comparable to the turbid river-waters often filtered elsewhere,
and their tendency to choke the filters is consequently much less. At
Rotterdam and Schiedam, where the raw water is drawn from the Maas, as
the principal stream of the Rhine is called in Holland, river-sand of
much larger grain size is employed. It is obtained by dredging in the
river and is never washed, new sand always being employed for refilling.

The average results of the complete analyses of sands from ten leading
works are shown in the table on page 28. These figures are the average
of all the analyses for the respective places, except that one sample
from the Lambeth Co., which was not a representative one, was omitted.

The London companies were selected for this comparison both on
account of their long and favorable records in filtering the polluted
waters of the Thames and Lea, and because they are subject to close
inspection; and there is ample evidence that the filtration obtained is
good—evidence which is often lacking in the smaller and less closely
watched works. For the German works Altona was selected because of
its escape from cholera in 1892, due to the efficient action of its
filters, and Stralau because of its long and favorable record when
filtering the much-polluted Spree water. These two works also have
perhaps contributed more to the modern theories of filtration than all
the other works in existence. The remaining works are included because
they are comparatively new, and have been constructed with the greatest
care and attention to details throughout, and the results obtained are
most carefully recorded.

Some of the most interesting of these results are shown graphically on
page 29. The method of plotting is that described in Appendix III.

TABLE SHOWING THE AVERAGE PER CENT OF THE GRAINS FINER THAN VARIOUS
SIZES IN SANDS FROM LEADING WORKS.

--------------+----------------------------------------------------
| Per Cent by Weight Finer than
+------+------+------+-----+-----+-----+-----+-------
|0.106 |0.186 |0.316 |0.46 |0.93 |2.04 |3.89 |5.89
| mm. | mm. | mm. | mm. | mm. | mm. | mm. | mm.
--------------+------+------+------+-----+-----+-----+-----+-------
East London | 0.2 | 0.5 | 3.6 |22.2 |69.7 |89.8 |95.0 |99.0
Grand Junction| 0 | 0.2 | 3.1 |17.4 |47.1 |68.2 |84.7 |93.6
Southwark and | | | | | | | |
Vauxhall | | 0.7 | 8.0 |34.1 |69.7 |83.5 |90.0 |94.0
Lambeth | 0 | 0.5 | 5.5 |26.6 |63.0 |79.2 |88.0 |94.3
Chelsea | 0 | 0.1 | 5.0 |28.6 |63.0 |76.7 |86.0 |93.6
Hamburg | 0.2 | 1.5 |10.9 |33.2 |74.4 |95.7 |99.5 |
Altona | 0.1 | 1.1 | 7.8 |28.7 |72.1 |92.1 |95.8 |
Stralau | | 0.3 | 7.0 |37.3 |86.9 |95.4 |97.6 |
Tegel | | 0.2 | 4.5 |35.4 |94.3 |98.5 |99.1 |
Müggel | 0.1 | 0.5 | 7.9 |33.6 |79.7 |94.3 |98.5 |
+------+------+------+-----+-----+-----+-----+-------
Average of all| 0.06 | 0.56 | 6.33 |29.71|71.99|87.34|93.42|(97.45)
--------------+------+------+------+-----+-----+-----+-----+-------

AVERAGE EFFECTIVE SIZE, UNIFORMITY COEFFICIENT, AND ALBUMINOID AMMONIA
IN SANDS FROM TEN LEADING WORKS.

I. LONDON FILTERS.
----------------------+--------------+------------+-------------------
| Effective | Uniformity |Albuminoid Ammonia.
| Size; 10% |Coefficient.+------------+------
| Finer than | | Dirty Sand.|Washed
|(Millimeters).| | | Sand.
----------------------+--------------+------------+------------+------
East London | 0.40 | 2.0 | 26.00 | 8.60
Grand Junction | 0.40 | 3.6 | 10.00 | 2.70
Southwark and Vauxhall| 0.34 | 2.5 | | 3.90
Lambeth | 0.36 | 2.4 | | 2.60
Chelsea | 0.36 | 2.4 | | 2.10
+--------------+------------+------------+------
Average | 0.37 | 2.6 | 18.00 | 3.98
----------------------+--------------+------------+------------+------

II. GERMAN WORKS.
----------------------+--------------+------------+------------+------
Stralau | 0.34 | 1.7 | 12.20 | 4.00
Tegel | 0.37 | 1.6 | 11.00 | 3.00
Müggel | 0.34 | 2.0 | 10.80 | 0.80
Altona | 0.34 | 2.3 | 9.00 | 1.50
Hamburg | 0.31 | 2.3 | 8.20 | 1.07
+--------------+------------+------------+------
Average | 0.34 | 2.0 | 10.25 | 2.07
----------------------+--------------+------------+------------+------

[Illustration: PLACING SAND IN A FILTER, HAMBURG.

[_To face page 28._]]

The averages show the effective size of the English sands to be
slightly greater than that of the German sands—0.37 instead of 0.34
mm.—but the difference is very small. The entire range for the ten
works is only from 0.31 to 0.40 mm., and these may be taken as the
ordinary limits of effective size of the sands employed in the best
European works. The average for the other sixteen works given above,
including dune-sands, is 0.31 mm., or, omitting the dune-sands, 0.34 mm.

[Illustration: FIG. 3_a_.—SAND ANALYSIS SHEET, WITH ANALYSES OF SEVERAL
EUROPEAN FILTER SANDS.]

It is important that filter sands should be free from lime. When water
is filtered through such sands, no increase in hardness results. When,
however, water is filtered through sand containing lime, some of it
is usually dissolved and the water is made harder. The amount of lime
taken up in this way depends both upon the character of the sand, and
upon the solvent power of the water; and it does not necessarily follow
that a sand containing lime cannot be used for filtration, but a sand
nearly free from lime is to be preferred.

The presence of lime in sand can usually be detected by moistening it
with hydrochloric acid. The evolution of gas shows the presence of
lime. Some idea of the amount of lime can be obtained from the amount
of gas given off, and the appearance of the sample after the treatment,
but chemical analysis is necessary to determine correctly the amount.

Experiments with filters at Pittsburg were made with sand containing
1.3 per cent of lime, the result being that the hardness of the water
was increased about one part in 100,000; but the amount of lime in the
sand was so small that it would be washed out after a time, and then
the hardening effect would cease. Larger amounts of lime would continue
their action for a number of years and would be more objectionable.

Turning to the circumstances which influence the selection of the
sand size, we find that both the quality of the effluent obtained by
filtration and the cost of filtration depend upon the size of the
sand-grains.

With a fine sand the sediment layer forms more quickly and the removal
of bacteria is more complete, but, on the other hand, the filter clogs
quicker and the dirty sand is more difficult to wash, so that the
expense is increased.

EFFECT OF SIZE OF GRAIN UPON EFFICIENCY OF FILTRATION.

It is frequently stated that it is only the sediment layer which
performs the work of filtration, and that the sand which supports
it plays hardly a larger part than does the gravel which carries
the sand, and under some circumstances this is undoubtedly the case.
Nevertheless sand in itself, without any sediment layer, especially
when not too coarse and not in too thin layers, has very great
purifying powers, and, in addition, acts as a safeguard by positively
preventing excessive rates of filtration on account of its frictional
resistance. As an illustration take the case of a filter of sand with
an effective size of 0.35 mm. and the minimum thickness of sand allowed
by the German Board of Health, namely, one foot, and let us suppose
that with clogging the loss of head has reached two feet to produce
the desired velocity of 2.57 million gallons per acre daily. Suppose
now that by some accident the sediment layer is suddenly broken or
removed from a small area, the water will rush through this area,
until a new sediment layer is formed, at a rate corresponding to the
size, pressure, and depth of the sand, or 260 million gallons per
acre daily—a hundred times the standard rate. Under these conditions
the passing water will not be purified, but will pollute the entire
effluent from the filter. Under corresponding conditions, with a deep
filter of fine sand, say with an effective size of 0.20 mm. and 5 feet
deep, the resulting rate would be only 17 million gallons per acre
daily, or less than seven times the normal, and with the water passing
through the full depth of fine sand, the resulting deterioration in the
effluent before the sand again became so clogged as to reduce the rate
to nearly the normal, would be hardly appreciable.

The results at Lawrence have shown that with very fine sands 0.09 and
0.14 mm., and 4 to 5 feet deep, with the quantity of water which can
practically be made to pass through them, it is almost impossible to
drive more than an insignificant fraction of the bacteria into the
effluent. Even when the sands are entirely new, or have been scraped or
disturbed in the most violent way, the first effluent passing, before
the sediment layer could have been formed, is of good quality. Still
finer materials, 0.04 to 0.06 mm., as far as could be determined,
secured the absolute removal of all bacteria, but the rates of
filtration which were possible were so low as to preclude their
practical application.

With coarser sands, as long as the filter is kept at a steady rate of
filtration, without interruptions of any kind, entirely satisfactory
results are often obtained, although never quite so good as with
the finer sands. Thus at Lawrence the percentages of bacteria (_B.
prodigiosus_) appearing in the effluents under comparable conditions
were as follows:

1892 1893
With effective grain size 0.38 mm .... 0.16
With effective grain size 0.29 mm .... 0.16
With effective grain size 0.26 mm .... 0.10
With effective grain size 0.20 mm 0.13 0.01
With effective grain size 0.14 mm 0.04 0.03
With effective grain size 0.09 mm 0.02 0.02

We may thus conclude that fine sands give normally somewhat better
effluents than coarser ones, and that they are much more likely to
give at least a tolerably good purification under unusual or improper
conditions.

EFFECT OF GRAIN SIZE UPON FREQUENCY OF SCRAPING.

The practical objection to the use of fine sand is that it becomes
rapidly clogged, so that filters require to be scraped at shorter
intervals, and the sand washing is much more difficult and expensive.
The quantities of water filtered between successive scrapings at
Lawrence in millions of gallons per acre under comparable conditions
have been as follows:

1892 1893
Effective size of sand grain 0.38 mm .... 79
Effective size of sand grain 0.29 mm .... 70
Effective size of sand grain 0.26 mm .... 57
Effective size of sand grain 0.20 mm 58 ....
Effective size of sand grain 0.14 mm 45 49
Effective size of sand grain 0.09 mm 24 14

The increase in the quantities passed between scrapings with increasing
grain size is very marked.

With the fine sands, the depth to which the sand becomes dirty is much
less than with the coarse sands, but as it is not generally practicable
to remove a layer of sand less than about 0.6 inch thick, even when the
actual clogged layer is thinner than this, the full quantity of sand
has to be removed; and the quantities of sand to be removed and washed
are inversely proportional to the quantities of water filtered between
scrapings. On the other hand, with very coarse sands the sediment
penetrates the sand to a greater depth than the 0.6 inch necessarily
removed, so that a thicker layer of sand has to be removed, which
may more than offset the longer interval. This happens occasionally
in water-works, and a sand coarse enough to allow it occur is always
disliked by superintendents, and is replaced with finer sand as soon as
possible. It is obvious that the minimum expense for cleaning will be
secured with a sand which just does not allow this deep penetration,
and I am inclined to think that the sizes of the sands in use have
actually been determined more often than otherwise in this way, and
that the coarsest samples found, having effective sizes of about 0.40
mm., represent the practical limit to the coarseness of the sand,
and that any increase above this size would be followed by increased
expense for cleaning as well as by decreased efficiency.

SELECTION OF SAND.

In selecting a sand for filtration, when it is considered that repeated
washings will remove some of the finest particles, and so increase
slightly the effective size, a new sand coarser than 0.35 mm. would
hardly be selected. Perhaps 0.20 might be given as a suitable lower
limit. For comparatively clear lake- or reservoir-waters a finer
sand could probably be used than would be the case with a turbid
river-water. A mixed sand having a uniformity coefficient above 3.0
would be difficult to wash without separating it into portions of
different sizes, and, in general, the lower the coefficient, that is,
the more uniform the grain sizes, the better. Great pains should be
taken to have the sand of the same quality throughout, especially in
the same filter, as any variations in the grain sizes would lead to
important variations in the velocity of filtration, the coarser sands
passing more than their share of water (in proportion to the square of
the effective sizes) and with reduced efficiency.

At Lawrence a sufficient quantity of natural sand was found of the
grade required; but where suitable material cannot be so obtained it
is necessary to use other methods. A mixed material can be screened
from particles which are too large, and can be washed to free it from
its finer portions, and in this way a good sand can be prepared, if
necessary, from what might seem to be quite unpromising material. The
methods of sand-washing will be described in Chapter V.

THICKNESS OF THE SAND LAYER.

The thickness of the sand layer is made so great that when it is
repeatedly scraped in cleaning the sand will not become too thin for
good filtration for a considerable time. When this occurs the removed
sand must be replaced with clean sand. The original thickness of the
sand in European filters is usually from 24 to 48 inches, thicknesses
between 30 and 40 inches being extremely common, and this is reduced
before refilling to from 12 to 24 inches. The Imperial Board of Health
of Germany has fixed 12 inches as a limit below which the sand should
never be scraped, and a higher limit is recommended wherever possible.

A thick sand layer has the same steadying action as a fine sand, and
tends to prevent irregularities in the rate of filtration in proportion
to its frictional resistance, and that without increasing the frequency
of cleaning; but, on the other hand, it increases the necessary height
of the filter, throughout, and consequently the cost of construction.

In addition to the steadying effect of a deep sand layer, some
purification takes place in the lower part of the sand even with a good
sediment layer on the surface, and the efficiency of deep filters is
greater than that of shallow ones.

Layers of finer materials, as fine sand or loam, in the lower part
of a filter, which would otherwise give increased efficiency without
increasing the operating expenses, cannot be used. Their presence
invariably gives rise sooner or later to sub-surface clogging at the
point of junction with the coarser sand, as has been found by repeated
tests at Lawrence as well as in some of the Dutch filters where such
layers were tried; and as there is no object in putting a coarser sand
under a finer, the filter sand is best all of the same size and quality
from top to bottom.

UNDERDRAINING.

The underdrains of a filter are simply useful for collecting the
filtered water; they play no part in the purification. One of the first
requirements of successful filtration is that the rate of filtration
shall be practically the same in all parts of the filter. This is most
difficult to secure when the filter has just been cleaned and the
friction of the sand layer is at a minimum. If the friction of the
water in entering and passing through the underdrains is considerable,
the more remote parts of the filters will work under less pressure,
and will thus do less than their share of the work, while the parts
near the outlet will be overtaxed, and filtering at too high rates will
yield poor effluents.

To avoid this condition the underdrains must have such a capacity
that their frictional resistance will be only a small fraction of the
friction in the sand itself just after cleaning.

GRAVEL LAYERS.

The early filters contained an enormous quantity of gravel, but the
quantity has been steadily reduced in successive plants. Thus in 1866
Kirkwood, as a result of his observations, recommended the use of a
layer four feet thick, and in addition a foot of coarse sand, while
at the present time new filters rarely have more than two feet of
gravel. Even this quantity seems quite superfluous, when calculations
of its frictional resistance are made. Thus a layer of gravel with an
effective size of 20 mm.[5] (which is much finer than that generally
employed) only 6 inches thick will carry the effluent from a filter
working at a rate of 2.57 million gallons per acre daily for a distance
of 8 feet (that is, with underdrains 16 feet apart), with a loss of
head of only 0.001 foot, and for longer distances tile drains are
cheaper than gravel. To prevent the sand from sinking into the coarse
gravel, intermediate sizes of gravel must be placed between, each grade
being coarse enough so that there is no possibility of its sinking into
the layer below. The necessary thickness of these intermediate layers
is very small, the principal point being to have a layer of each grade
at every point. Thus on the 6 inches of 20 mm. gravel mentioned above,
three layers of two inches each, of 8 and 3 mm. gravel and coarse
sand, with a total height of six inches, or other corresponding and
convenient depths and sizes, would, if carefully placed, as effectually
prevent the sinking of the filter sand into the coarse gravel as the
much thicker layers used in the older plants.

The gravel around the drains should receive special attention. Larger
stones can be here used with advantage, taking care that adequate
spaces are left for the entrance of the water into the drains at a low
velocity, and to make everything so solid in this neighborhood that
there will be no chance for the stones to settle which might allow the
sand to reach the drains.

[Illustration: RECONSTRUCTING THE UNDERDRAINAGE SYSTEM OF A FILTER
AFTER 25 YEARS OF USE, BREMEN.]

[Illustration: PLACING SAND IN A FILTER, CHOISY LE ROI (PARIS).

[_To face page 36._]]

At the Lawrence filter, at Königsberg in Prussia, at Amsterdam and
other places, the quantity of gravel is reduced by putting the drains
in trenches, so that the gravel is reduced from a maximum thickness
at the drain to nothing half way between drains. The economy of the
arrangement, however, as far as friction is concerned is not so great
as would appear at first sight, and the cost of the bottom may be
increased; but on the other hand it gives a greater depth of gravel for
covering the drains with a small total amount of gravel.

As even a very small percentage of fine material is capable of
getting in the narrow places and reducing the carrying power of the
gravel, it is important that all such matters should be carefully
removed by washing before putting the gravel in place. In England and
Germany gravel is commonly screened for use in revolving cylinders of
wire-cloth of the desired sizes, on which water is freely played from
numerous jets, thus securing perfectly clean gravel. In getting gravel
for the Lawrence filter, an apparatus was used, in which advantage was
taken of the natural slope of the gravel bank to do the work, and the
use of power was avoided. The respective grades of gravel obtained were
even in size, and reasonably free from fine material, but it was deemed
best to wash them with a hose before putting them in the filter.

To calculate the frictional resistance of water in passing gravel, we
may assume that for the very low velocities which are actually found in
filters the quantity of water passing varies directly with the head,
which for these velocities is substantially correct, although it would
not be true for higher rates, especially with the coarser gravels.[6]
In the case of parallel underdrains the friction from the middle point
between drains to the drains may be calculated by the formula:

Total head = (1/2)[(Rate of filtration × (1/2 distance between
drains)^2)/(Average depth of gravel × discharge coefficient)].

The discharge coefficient for any gravel is 1000 times the quantity

of water which will pass when _h_/_l_ is 1/1000 expressed in million
gallons per acre daily. The approximate values of this coefficient for
different-sized gravels are as follows:

VALUES OF DISCHARGE COEFFICIENT.

For gravel with effective size 5 mm _c_ = 23,000
For gravel with effective size10 mm _c_ = 65,000
For gravel with effective size15 mm _c_ = 110,000
For gravel with effective size20 mm _c_ = 160,000
For gravel with effective size25 mm _c_ = 230,000
For gravel with effective size30 mm _c_ = 300,000
For gravel with effective size35 mm _c_ = 390,000
For gravel with effective size40 mm _c_ = 480,000

Example: What is the loss of head in the gravel at a rate of filtration
of 2 million gallons per acre daily, with underdrains 20 feet apart,
where the supporting gravel has an effective size of 35 millimeters,
and is uniformly 1 ft. deep?

Total head = (1/2)[(2 × 10^2)/(1 × 390,000)] = .000256 ft.

The total friction would be the same with the same average depth of
gravel whether it was uniformly 1 foot deep, or decreasing from 1.5 at
the drains to 0.5 in the middle, or from 2.0 to 0. The reverse case
with the gravel layer thicker in the middle than at the drains does not
occur and need not be discussed.

The depth of gravel likely to be adopted as a result of this
calculation, when the drains are not too far apart, will be much less
than that actually used in most European works, but as the two feet or
more there employed are, I believe, simply the result of speculation,
there is no reason for following the precedent where calculations show
that a smaller quantity is adequate.

The reason for recommending a thin lower layer of coarse gravel, which
alone is assumed to provide for the lateral movement of the water,
is that if more than about six inches of gravel is required to give a
satisfactory resistance, it will almost always be cheaper to use more
drains instead of more gravel; and the reason for recommending thinner
upper layers for preventing the sand from settling into the coarse
gravel is that no failures of this portion of filters are on record,
and in the few instances where really thin layers have been used the
results have been entirely satisfactory. In Königsberg filters were
built by Frühling,[7] in which the sand was supported by five layers
of gravel of increasing sizes, respectively 1.2, 1.2, 1.6, 2.0, 3.2,
or, together, 9.2 inches thick, below which there were an average of
five inches of coarse gravel. These were examined after eight years of
operation and found to be in perfect order.

At the Lawrence Experiment Station filters have been repeatedly
constructed with a total depth of supporting gravel layers not
exceeding six inches, and among the scores of such filters there has
not been a single failure, and so far as they have been dug up there
has never been found to have been any movement whatever of the sand
into the gravel. The Lawrence city filter, built with corresponding
layers, has shown no signs of being inadequately supported. In
arranging the Lawrence gravel layers care has always been taken that no
material should rest on another material more than three or four times
as coarse as itself, and that each layer should be complete at every
point, so that by no possibility could two layers of greater difference
in size come together. And it is believed that if this is carefully
attended to, no trouble need be anticipated, however thin the single
layers may be.

UNDERDRAINS.

The most common arrangement, in other than very small filters, is to
have a main drain through the middle of the filter, with lateral
drains at regular intervals from it to the sides. The sides of the main
drain are of brick, laid with open joints to admit water freely, and
the top is usually covered with stone slabs. The lateral drains may be
built in the same way, but tile drains are also used and are cheaper.
Care must be taken with the latter that ample openings are left for the
admission of water at very low velocities. It is considered desirable
to have these drains go no higher than the top of the coarsest gravel;
and this will often control the depth of gravel used. If they go
higher, the top must be made tight to prevent the entrance of the fine
gravels or sand. Sometimes they are sunk in part or wholly (especially
the main drain) below the floor of the filter. With gravel placed in
waves, that is, thicker over the drains than elsewhere, as mentioned
above, the drains are covered more easily than with an entirely
horizontal arrangement. When this is done, the floor of the filter is
trenched to meet the varying thickness of gravel, so that the top of
the latter is level, and the sand has a uniform thickness.

Many filters (Lambeth, Brunswick, etc.) are built with a double bottom
of brick, the upper layer of which, with open joints, supports the
gravel and sand, and is itself supported by numerous small arches or
other arrangements of brick, which serve to carry the water to the
outlet without other drains. This arrangement allows the use of a
minimum quantity of gravel, but is undoubtedly more expensive than the
usual form, with only the necessary quantity of gravel; and I am unable
to find that it has any corresponding advantages.

The frictional resistance of underdrains requires to be carefully
calculated; and in doing this quite different standards must be
followed from those usually employed in determining the sizes
of water-pipes, as a total frictional resistance of only a few
hundredths of a foot, including the velocity head, may cause serious
irregularities in the rate of filtration in different parts of the
filter.

The sizes of the underdrains differ very widely in proportion to the
sizes of the filters in European works, some of them being excessively
large, while in other cases they are so small as to suggest a doubt as
to their allowing uniform rates of filtration, especially just after
cleaning.

I would suggest the following rules as reasonably sure to lead to
satisfactory results without making an altogether too lavish provision:
In the absence of a definite determination to run filters at some
other rate, calculate the drains for the German standard rate of a
daily column of 2.40 meters, equal to 2.57 million gallons per acre
daily. This will insure satisfactory work at all lower rates, and
no difficulty on account of the capacity of the underdrains need be
then anticipated if the rate is somewhat exceeded. The area for a
certain distance from the main drain depending upon the gravel may be
calculated as draining directly into it, provided there are suitable
openings, and the rest of the area is supposed to drain to the nearest
lateral drain.

In case the laterals are round-tile drains I would suggest the
following limits to the areas which they should be allowed to drain:

Diameter of Drain. To Drain an Area not Corresponding Velocity of
Exceeding Water in Drain.
4 inches 290 square feet. 0.30 foot.
6 inches 750 square feet. 0.35 foot.
8 inches 1530 square feet. 0.40 foot.
10 inches 2780 square feet. 0.46 foot.
12 inches 4400 square feet. 0.51 foot.

And for larger drains, including the main drains, their cross-sections
at any point should be at least 1/6000 of the area drained, giving a
velocity of 0.55 foot per second with the rate of filtration mentioned
above.

The total friction of the underdrains from the most remote points
to the outlet will be friction in the gravel, plus friction in the
lateral drains, plus the friction in main drain, plus the velocity head.

[Illustration: FIG. 4.—PLAN OF ONE OF THE HAMBURG FILTERS, SHOWING
FRICTIONAL RESISTANCE OF THE UNDERDRAINS.]

I have calculated in this way the friction of one of the Hamburg
filters for the rate of 1,600,000 gallons per acre daily at which it
is used. The friction was calculated for each section of the drains
separately, so that the friction from intermediate points was also
known. Kutter’s formula was used throughout with _n_ = 0.013. On
the accompanying plan of the filter I have drawn the lines of equal
frictional resistance from the junction of the main drain with the last
laterals. My information was incomplete in regard to one or two points,
so that the calculation may not be strictly accurate, but it is nearly
so and will illustrate the principles involved.

[Illustration: CONSTRUCTING THE UNDERDRAINAGE SYSTEM OF A FILTER,
HAMBURG.

[_To face page 42._]
]

The extreme friction of the underdrains is 11 millimeters = 0.036 foot.

The frictional resistance of the sand 39 inches thick, effective size
0.32 mm. and rate 1.60 million gallons per acre daily, when absolutely
free from clogging, is by the formula, page 21, 15mm., or .0490
foot, when the temperature is 50°. Practically there is some matter
deposited upon the surface of the sand before filtration starts, and
further, after the first scraping, there is some slight clogging in the
sand below the layer removed by scraping. We can thus safely take the
minimum frictional resistance of the sand including the surface layer
at .07 foot. The average friction of the underdrains for all points
is about .023 foot and the friction at starting will be .07 + .023 =
.093 foot (including the friction in the last section to the effluent
well where the head is measured, .100 foot, but the friction beyond the
last lateral does not affect the uniformity of filtration). The actual
head on the sand close to the outlet will be .093 and the rate of
filtration .093/.070 · 1.60 = 2.12. The actual head at the most remote
point will be .093 - .036 = .057, and the rate of filtration will there
be .057/.070 · 160 = 1.30 million gallons per acre daily. The extreme
rates of filtration are thus 2.12 and 1.30, instead of the average rate
of 1.60. As can be seen from the diagram, only very small areas work
at these extreme rates, the great bulk of the area working at rates
much nearer the average. Actually the filter is started at a rate below
1.60, and the nearest portion never filters so rapidly as 2.12, for
when the rate is increased to the standard, the sand has become so far
clogged that the loss of head is more than the .07 foot assumed, and
the differences in the rates are correspondingly reduced. Taking this
into account, it would not seem that the irregularities in the rate of
filtration are sufficient to affect seriously the action of the filter.
They could evidently have been largely reduced by moderately increasing
the sizes of the lower ends of the underdrains, where most of the
friction occurs with the high velocities (up to .97 foot) which there
result.

The underdrains of the Warsaw filters were designed by Lindley to have
a maximum loss of head of only .0164 foot when filtering at a rate of
2.57, which gives a variation of only 10 per cent in the rates with the
minimum loss of head of .169 foot in the entire filter assumed by him.
The underdrains of the Berlin filters, according to my calculations,
have .020 to .030 foot friction, of which an unusually large proportion
is in the gravel, owing to the excessive distances, in some cases over
80 feet, which the gravel is required to carry the water. In this case,
using less or finer gravel would obviously have been fatal, but the
friction as well as the expense of construction would be much reduced
by using more drains and less gravel.

The underdrains might appropriately be made slightly smaller, with a
deep layer of fine sand, than under opposite conditions, as in this
case the increased friction in the drains would be no greater in
proportion to the increased friction in the sand itself.

The underdrains of a majority of European filters have water-tight
pipes connecting with them at intervals, and going up through the sand
and above the water, where they are open to the air. These pipes were
intended to ventilate the underdrains and allow the escape of air when
the filter is filled with water introduced from below. It may be said,
however, that in case the drains are surrounded by gravel and there is
an opportunity for the air to pass from the top of the drain into the
gravel, it will so escape without special provision being made for it,
and go up through the sand with the much larger quantity of air in the
upper part of the gravel which is incapable of being removed by pipes
connecting with the drains.

These ventilator pipes where they are used are a source of much
trouble, as unfiltered water is apt to run down through cracks in the
sand beside them, and, under bad management, unfiltered water may even
go down through the pipes themselves. I am unable to find that they
are necessary, except with underdrains so constructed that there is
no other chance for the escape of air from the tops of them, or that
they serve any useful purpose, while there are positive objections to
their use. In some of the newer filters they have been omitted with
satisfactory results.

DEPTH OF WATER ON THE FILTERS.

In the older works with but crude appliances for regulating the rate of
filtration and admission of raw water, a considerable depth of water
was necessary upon the filter to balance irregularities in the rates
of filtration; the filter was made to be, to a certain extent, its own
storage reservoir. When, however, appliances of the character to be
described in Chapter IV are used for the regulation of the incoming
water, and with a steady rate of filtration, this provision becomes
quite superfluous.

With open filters a depth of water in excess of the thickness of any
ice likely to be formed is required to prevent disturbance or freezing
of the sand in winter. It is also frequently urged that with a deep
water layer on the filter the water does not become so much heated in
summer, but this point is not believed to be well taken, for in any
given case the total amount of heat coming from the sun to a given area
is constant, and the quantity of water heated in the whole day—that
is, the amount filtered—is constant, and variations in the quantity
exposed at one time will not affect the average resulting increase in
temperature. If the same water remained upon the filter without change
it would of course be true that a thin layer would be heated more than
a deep one, but this is not the case.

It is also sometimes recommended that the depth of water should be
sufficient to form a sediment layer before filtration starts, but this
point would seem to be of doubtful value, especially where the filter
is not allowed to stand a considerable time with the raw water upon it
before starting filtration.

It is also customary to have a depth of water on the filter in excess
of the maximum loss of head, so that there can never be a suction in
the sand just below the sediment layer. It may be said in regard to
this, however, that a suction below is just as effective in making the
water pass the sand as an equal head above. At the Lawrence Experiment
Station filters have been repeatedly used with a water depth of only
from 6 to 12 inches, with losses of head reaching 6 feet, without the
slightest inconvenience. The suction only commences to exist as the
increasing head becomes greater than the depth of water, and there is
no way in which air from outside can get in to relieve it. In these
experimental filters in winter, when the water is completely saturated
with air, a small part of the air comes out of the water just as it
passes the sediment layer and gets into reduced pressure, and this
air prevents the satisfactory operation of the filters. But this is
believed to be due more to the warming and consequent supersaturation
of the water in the comparatively warm places in which the filters
stand than to the lack of pressure, and as not the slightest trouble
is experienced at other seasons of the year, it may be questioned
whether there would be any disadvantage at any time in a corresponding
arrangement on a large scale where warming could not occur.

The depths of water actually used in European filters with the full
depth of sand are usually from 36 to 52 inches. In only a very few
unimportant cases is less than the above used, and only a few of the
older works use a greater depth, which is not followed in any of the
modern plants. As the sand becomes reduced in thickness by scraping,
the depth of water is correspondingly increased above the figures given
until the sand is replaced. The depth of water on the German covered
filters is quite as great as upon corresponding open filters. Thus the
Berlin covered filters have 51, while the new open filters at Hamburg
have only 43 inches.

CHAPTER IV.

RATE OF FILTRATION AND LOSS OF HEAD.

The rate of filtration recommended and used has been gradually reduced
during the past thirty years. In 1866 Kirkwood found that 12 vertical
feet per day, or 3.90 million gallons per acre daily, was recommended
by the best engineers, and was commonly followed as an average rate.
In 1868 the London filters averaged a yield of 2.18 million gallons[8]
per acre daily, including areas temporarily out of use, while in 1885
the quantity had been reduced to 1.61. Since that time the rate has
apparently been slightly increased.

The Berlin filters at Stralau constructed in 1874 were built to filter
at a rate of 3.21 million gallons per acre daily. The first filters at
Tegel were built for a corresponding rate, but have been used only at
a rate of 2.57, while the more recent filters were calculated for this
rate. The new Hamburg filters, 1892-3, were only intended to filter
at a rate of 1.60 million gallons per acre daily. These in each case
(except the London figures) are the standard rates for the filter-beds
actually in service.

In practice the area of filters is larger than is calculated from
these figures, as filters must be built to meet maximum instead of
average daily consumptions, and a portion of the filtering area usually
estimated at from 5 to 15 per cent, but in extreme cases reaching 50
per cent, is usually being cleaned, and so is for the time out of
service. In some works also the rate of filtration on starting a filter
is kept lower than the standard rate for a day or two, or the first
portion of the effluent, supposed to be of inferior quality, is

wasted, the amount so lost reaching in an extreme case 9 to 14 per
cent of the total quantity of water filtered.[9] In many of the older
works also, there is not storage capacity enough for filtered water to
balance the hourly fluctuations in consumption, and the filters must be
large enough to meet the maximum hourly as well as the maximum daily
requirements. For these reasons the actual quantity of water filtered
in a year is only from 50 to 75 per cent of what would be the case if
the entire area of the filters worked constantly at the full rate. A
statement of the actual yields of a number of filter plants is given in
Appendix IV. The figures for the average annual yields can be taken as
quite reliable. The figures given for rate, in many cases, have little
value, owing to the different ways in which they are calculated at
different places. In addition most of the old works have no adequate
means of determining what the rate at any particular time and for a
single filter really is, and statements of average rates have only
limited value. The filters at Hamburg are not allowed to filter faster
than 1.60 or those at Berlin faster than 2.57 million gallons per acre
daily, and adequate means are provided to secure this condition. Other
German works aim to keep within the latter limit. Beyond this, unless
detailed information in regard to methods is presented, statements of
rate must be taken with some allowance.

EFFECT OF RATE UPON COST OF FILTRATION.

The size of the filters required, and consequently the first cost,
depends upon the rate of filtration, but with increasing rates the cost
is not reduced in the same proportion as the increase in rate, since
the allowance for area out of use is sensibly the same for high and low
rates, and in addition the operating expenses depend upon the quantity
filtered and not upon the filtering area. Thus, to supply 10 million
gallons at a maximum rate of 2 million gallons per acre daily we should
require 10 ÷ 2 = 5 acres + 1 acre reserve for cleaning = 6 acres, while
with a rate twice

as great, and with the same reserve (since the same amount of cleaning
must be done, as will be shown below), we should require 10 ÷ 4 + 1
= 3.5 acres, or 58 per cent of the area required for the lower rate.
Thus beyond a certain point increasing the rate does not effect a
corresponding reduction in the first cost.

The operating cost for the same quantity of water filtered does not
appear to be appreciably affected by the rate. It is obvious that
at high rates filters will became clogged more rapidly, and will
so require to be scraped oftener than at low rates, and it might
naturally be supposed that the clogging would increase more rapidly
than the rates, but this does not seem to be the case. At the Lawrence
Experiment Station, under strictly parallel conditions and with
identically the same water, filters running at various rates became
clogged with a rapidity directly proportional to the rates, so that
the quantities of water filtered between scrapings under any given
conditions are the same whether the rate is high or low.

The statistics bearing upon this point are interesting, if not entirely
conclusive. There were eleven places in Germany filtering river waters,
from which statistics were available for the year 1891-92. Of these
there were four places with high rates, Lübeck, Stettin, Stuttgart, and
Magdeburg, yielding 3.70 million gallons per acre daily, which filtered
on an average 59 million gallons per acre between scrapings. Three
other places, Breslau, Altona, and Frankfurt, yielding 1.85, passed
on an average 55 million gallons per acre between scrapings, and four
other places, Bremen, Königsberg, Brunswick and Posen, yielding 1.34
million gallons per acre daily, passed only 40 million gallons per
acre between scrapings. The works filtering at the highest rates thus
filtered more water in proportion to the sand clogged than did those
filtering more slowly, but I cannot think that this was the result of
the rate. It is more likely that some of the places have clearer waters
than others, and that this both allows the higher rate and causes less
clogging than the more turbid waters.

EFFECT OF RATE UPON EFFICIENCY OF FILTRATION.

The effect of the rate of filtration upon the quality of the effluent
has been repeatedly investigated. The efficiency almost uniformly
decreases rapidly with increasing rate. Fränkel and Piefke[10] first
found that with the high rates the number of bacteria passing some
experimental filters was greatly increased. Piefke[11] afterward
repeated these experiments, eliminating some of the features of the
first series to which objection was made, and confirmed the first
results. The results were so marked that Piefke was led to recommend
the extremely low limit of 1.28 million gallons per acre daily as the
safe maximum rate of filtration, but he has since repeatedly used 2.57
million gallons.

Kümmel,[12] on the other hand, in a somewhat limited series of
experiments, was unable to find any marked connection between the rate
and the efficiency, a rate of 2.57 giving slightly better results than
rates of either 1.28 or 5.14.

The admirably executed experiments made at Zürich in 1886-8 upon this
point, which gave throughout negative results, have but little value in
this connection, owing to the extremely low number of bacteria in the
original water.

At Lawrence in 1892 the following percentages of bacteria (_B.
prodigiosus_) passed at the respective rates:

--------+--------+-----------+---------------------------------------
No. of | Depth. | Effective | Rate. Millions gallons per acre daily.
Filter. | | Size of +-------+-------+-------+-------+-------
| | Sand. | 0.5 | 1.0 | 1.5 | 2.0 | 3.0
--------+--------+-----------+-------+-------+-------+-------+-------
| | | | | | |
33A | 60 | 0.14 | 0.002 | | | 0.040 |
34A | 60 | 0.09 | 0.001 | 0.005 | | 0.020 |
36A | 60 | 0.20 | | | 0.050 | | 0.050
37 | 60 | 0.20 | | | 0.010 | 0.130 |
38 | 24 | 0.20 | 0.018 | | 0.140 | 0.110 | 0.310
39 | 12 | 0.20 | 0.014 | 0.070 | | 0.080 | 0.520
40 | 12 | 0.20 | | 0.070 | | 0.090 |
42 | 12 | 0.20 | 0.016 | | | 0.150 | 0.550
--------+--------+-----------+-------+-------+-------+-------+-------
Average | 0.010 | 0.048 | 0.067 | 0.088 | 0.356
-----------------------------+-------+-------+-------+-------+-------

These results show a very marked decrease in efficiency with
increasing rates, the number of bacteria passing increasing in general
as rapidly as the square of the rate. The 1893 results also showed
decreased efficiency with high rates, but the range in the rates
under comparable conditions was less than in 1892, and the bacterial
differences were less sharply marked.

While the average results at Lawrence, as well as most of the European
experiments, show greatly decreased efficiency with high rates, there
are many single cases, particularly with deep layers of not too coarse
sand, where, as in Kümmel’s experiments, there seems to be little
connection between the rate and efficiency. An explanation of these
apparently abnormal results will be given in Chapter VI.

It is commonly stated[13] that every water has its own special rate of
filtration, which must be determined by local experiments, and that
this rate may vary widely in different cases. Thus it is possible that
the rate of 1.60 adopted at Hamburg for the turbid Elbe water, the rate
of 2.57 used at Berlin, and about the same at London for much clearer
river-waters, and the rate of 7.50 used at Zürich for the almost
perfectly clear lake-water are in each case the most suitable for the
respective waters. In other cases however, where rates much above 2.57
are used for river-waters, as at Lübeck and Stettin, there is a decided
opinion that these rates are excessive, and in these instances steps
are now being taken to so increase the filtering areas as to bring the
rates within the limit of 2.57 million gallons per acre daily.

From the trend of European practice it would seem that for American
river-waters the rate of filtration should not exceed 2.57 in place of
the 3.90 million gallons per acre daily recommended by Kirkwood, or
even that a somewhat lower rate might be desirable in some cases. Of
course, in addition to the area

necessary to give this rate, a reserve for fluctuating rates and for
cleaning should be provided, reducing the average yield to 2.00, 1.50,
or even less. In the case of water from clear lakes, ponds, or storage
reservoirs, especially when they are not subject to excessive sewage
pollution or to strong algæ growths, it would seem that rates somewhat
and perhaps in some cases very much higher (as at Zürich) could be
satisfactorily used.

THE LOSS OF HEAD.

The loss of head is the difference between the heads of the waters
above and below the sand layer, and represents the frictional
resistance of that layer. When a filter is quite free from clogging
this frictional resistance is small, but gradually increases with the
deposit of a sediment layer from the water filtered until it becomes so
great that the clogging must be removed by scraping before the process
can be continued. After scraping the loss of head is reduced to, or
nearly to, its original amount. With any given amount of clogging the
loss of head is directly proportional to the rate of filtration; that
is, if a filter partially clogged, filtering at a rate of 1.0, has a
frictional resistance of 0.5 ft., the resistance will be doubled by
increasing the rate to 2.00 million gallons per acre daily, provided
no disturbance of the sediment layer is allowed. This law for the
frictional resistance of water in sand alone also applies to the
sediment layer, as I have found by repeated tests, although in so
violent a change as that mentioned above, the utmost care is required
to make the change gradually and prevent compression or breaking of the
sediment layer. From this relation between the rate of filtration and
the loss of head it is seen that the regulation of either involves the
regulation of the other, and it is a matter of indifference which is
directly and which indirectly controlled.

REGULATION OF THE RATE AND LOSS OF HEAD IN THE OLDER FILTERS.

In the older works, and in fact in all but a few of the newest works,
the underdrains of the filters connect directly through a pipe with a
single gate with the pure-water reservoir or pump-well, which is so
built that the water in it may rise nearly or quite as high as that
standing upon the filter.

[Illustration: FIG. 5.—SIMPLEST FORM OF REGULATION: STRALAU FILTERS AT
BERLIN.]

A typical arrangement of this sort was used at the Stralau works at
Berlin (now discontinued), Fig. 5. With this arrangement the rate of
filtration is dependent upon the height of water in the reservoir or
pump-well, and so upon the varying consumption. When the water in the
receptacle falls with increasing consumption the head is increased,
and with it the rate of filtration, while, on the other hand, with
decreasing draft and rising water in the reservoir, the rate of
filtration decreases and would eventually be stopped if no water were
used. This very simple arrangement thus automatically, within limits,
adjusts the rate of filtration to the consumption, and at the same time
always gives the highest possible level of water in the pump-well, thus
also economizing the coal required for pumping.

In plants of this type the loss of head may be measured by floats
on little reservoirs built for that purpose, connected with the
underdrains; but more often there is no means of determining it,
although the maximum loss of head at any time is the difference between
the levels of the water on the filter and in the reservoir, or the
outlet of the drain-pipe, in case the latter is above the water-line
in the reservoir. The rate of filtration can only be measured with this
arrangement by shutting off the incoming water for a definite interval,
and observing the distance that the water on the filter sinks. The
incoming water is regulated simply by a gate, which a workman opens or
closes from time to time to hold the required height of water on the
filter.

The only possible regulation of the rate and loss of head is effected
by a partial closing of the gate on the outlet-pipe, by which the
freshly-cleaned filters with nearly-closed gates are kept from
filtering more rapidly than the clogged filters, the gates of which
are opened wide. Often, however, this is not done, and then the fresh
filters filter many times as rapidly as those which are partially
clogged.

A majority of the filters now in use are built more or less upon this
plan, including most of those in London and also the Altona works,
which had such a favorable record with cholera in 1892.

The invention and application of methods of bacterial examination in
the last years have led to different ideas of filtration from those
which influenced the construction of the earlier plants. As a result
it is now regarded as essential by most German engineers[14] that
each filter shall be provided with devices for measuring accurately
and at any time both the rate of filtration and the loss of head, and
for controlling them, and also for making the rate independent of
consumption by reservoirs for filtered water large enough to balance
hourly variations (capacity 1/4 to 1/3 maximum daily quantity) and low
enough so that they can never limit the rate of filtration by causing
back-water on the filters. These points are now insisted upon by the
German Imperial Board of Health,[15] and all new filters are built in
accordance with them, while most of the old works are being built over
to conform to the requirements.

APPARATUS FOR REGULATING THE RATE AND LOSS of HEAD.

Many appliances have been invented for the regulation of the rate and
loss of head. In the apparatus designed by Gill and used at both Tegel
and Müggel at Berlin the regulation is effected by partially closing
a gate through which the effluent passes into a chamber in which the
water-level is practically constant (Fig. 6). The rate is measured
by the height of water on the weir which serves as the outlet for
this second chamber into a third connecting with the main reservoir,
while the loss of head is shown by the difference in height of floats
upon water in the first chamber, representing the pressure in the
underdrains, and upon water in connection with the raw water on the
filter. From the respective heights of the three floats the attendant
can at any time see the rate of filtration and the loss of head, and
when a change is required it is effected by moving the gate.

[Illustration: FIG. 6.—REGULATION APPARATUS AT BERLIN (TEGEL).]

In the apparatus designed in 1866 by Kirkwood for St. Louis and never
built (Fig. 7) the loss of head was directly, and the rate indirectly,
regulated by a movable weir, which was to have been lowered from time
to time by the attendant to secure the required results. This plan is
especially remarkable as it meets the modern requirements of a regular
rate independent of rate of consumption and of the water-level in the
reservoir, and also allows continual measurements of both rate (height
of water on the weir) and head (difference in water-levels on filter
and in effluent chamber) to be made, and control of the same by the
position of the weir. Mr. Kirkwood found no filters in Europe with such
appliances, and it was many years after his report was published before
similar devices were used, but they are now regarded as essential.

[Illustration: FIG. 7.—REGULATION APPARATUS AND SECTION OF FILTER
RECOMMENDED FOR ST. LOUIS BY KIRKWOOD IN 1866.]

[Illustration: FIG. 8.—REGULATION APPARATUS USED AT HAMBURG.]

The regulators for new filters at Hamburg (Fig. 8) are built upon the
principle of Kirkwood’s device, but provision is made for a second
measurement of the water if desired by the loss of head in passing a
submerged orifice. Both the rate and loss of head are indicated by a
float on the first chamber connecting directly with the underdrain,
which at the same time indicates the head on a fixed scale, the zero of
which corresponds to the height of the water above the filter, and the
rate upon a scale moving with the weir, the zero of which corresponds
with the edge of the weir. The water on the filter is held at a
perfectly constant level.

The regulators in use at Worms and those recently introduced at
Magdeburg act upon the same principle, but the levels of the water on
the filters are allowed to fluctuate, and the weirs and in fact, the
whole regulating appliances are mounted on big floats in surrounding
chambers of water connecting with the unfiltered water on the filters.
I am unable to find any advantages in these appliances, and they are
much more complicated than the forms shown by the cuts.

APPARATUS FOR REGULATING THE RATE DIRECTLY.

[Illustration: FIG. 9.—LINDLEY’S REGULATION APPARATUS AT WARSAW,
RUSSIA.]

The above-mentioned regulators control directly the loss of head,
and only indirectly the rate of filtration. The regulators at Warsaw
were designed by Lindley to regulate the rate directly and make it
independent of the loss of head. The quantity of water flowing away
is regulated by a float upon the water in the effluent chamber,
which holds the top of the telescope outlet-pipe a constant distance
below the surface and so secures a constant rate. As the friction of
the filter increases the float sinks with the water until it reaches
bottom, when the filter must be scraped. A counter-weight reduces the
weight on the float, and at the same time allows a change in the rate
when desired. This apparatus is automatic. All of the other forms
described require to be occasionally adjusted by the attendant, but
the attention they require is very slight, and watchmen are always on
duty at large plants, who can easily watch the regulators. The Warsaw
apparatus is reported to work very satisfactorily, no trouble being
experienced either by leaking or sticking of the telescope-joint,
which is obviously the weakest point of the device, but fortunately a
perfectly tight joint is not essential to the success of the apparatus.
Regulators acting upon the same principle have recently been installed
at Zürich, where they are operating successfully.

Burton[16] has described an ingenious device designed by him for the
filters at Tokyo, Japan. It consists of a double acting valve of gun
metal (similar to that shown by Fig. 11), through which the effluent
must pass. This valve is opened and closed by a rod connecting with
a piston in a cylinder, the opposite sides of which connect with the
effluent pipe above and below a point where the latter is partially
closed, so that the valve is opened and closed according as the loss
of head in passing this obstruction is below or above the amount
corresponding to the desired rate of filtration.

The use of the Venturi meter in connection with the regulation of
filters would make an interesting study, and has, I believe, never been
considered.

[Illustration: REGULATOR-HOUSE, SHOWING RATE OF FILTRATION AND LOSS OF
HEAD ON THE OUTSIDE, BREMEN.]

[Illustration: INLET FOR ADMISSION OF RAW WATER TO A FILTER, EAST
LONDON.

[_To face page 58._]
]

APPARATUS FOR REGULATING THE HEIGHT OF WATER UPON FILTERS.

It will be seen by reference to the diagrams of the Berlin and Hamburg
effluent regulators (Figs. 6 and 8) that their perfect operation
is dependent upon the maintenance of a constant water-level upon
the filters. The old-fashioned adjustment of the inlet-gate by the
attendant is hardly accurate enough.

The first apparatus for accurately and automatically regulating the
level of the water upon the filters was constructed at Leeuwarden,
Holland, by the engineer, Mr. Halbertsma, who has since used a similar
device at other places, and improved forms of which are now used at
Berlin and at Hamburg.

At Berlin (Müggel) the water-level is regulated by a float upon the
water in the filter which opens or shuts a balanced double valve on
the inlet-pipe directly beneath, as shown in Fig. 10. It is not at all
necessary that this valve should shut water-tight; it is only necessary
that it should prevent the continuous inflow from becoming so great as
to raise the water-level, and for this reason loose, easily-working
joints are employed. The apparatus is placed in a little pit next to
the side of the filter, and the overflowing water is prevented from
washing the sand by paving the sand around it for a few feet.

[Illustration: FIG. 10.—REGULATION OF INFLOW USED AT MÜGGEL, BERLIN.]

At Hamburg the same result is obtained by putting the valve in a
special chamber outside of the filter and connected with the float by a
walking-beam (Fig. 11).

[Illustration: FIG. 11.—REGULATION OF INFLOW USED AT HAMBURG.]

The various regulators require to be protected from cold and ice by
special houses, except in the case of covered filters, where they can
usually be arranged with advantage in the filter itself. In regard to
the choice of the form of regulator for both the inlets and outlets of
filters, so far as I have been able to ascertain, each of the modern
forms described as in use performs its functions satisfactorily, and in
special cases any of them could properly be selected which would in the
local conditions be the simplest in construction and operation.

LIMIT TO THE LOSS OF HEAD.

The extent to which the loss of head is allowed to go before filters
are cleaned differs widely in the different works, some of the newer
works limiting it sharply because it is believed that low bacterial
efficiency results when the pressure is too great, although the
frequency of cleaning and consequently the cost of operation are
thereby increased.

At Darlington, England, I believe as a result of the German theories,
the loss of head is limited to about 18 inches by a masonry weir built
within the last few years. At Berlin, both at Tegel and Müggel, the
limit is 24 inches, while at the new Hamburg works 28 inches are
allowed. At Stralau in 1893 an effort was made to not exceed a limit
of 40 inches, but previously heads up to 60 inches were used, which
corresponds with the 56 inches used at Altona; and, in the other old
works, while exact information is not easily obtained because of
imperfect records, I am convinced that heads of 60 or even 80 inches
are not uncommon. At the Lawrence Experiment Station heads of 70 inches
have generally been used, although some filters have been limited to 36
and 24 inches.

In 1866 Kirkwood became convinced that the loss of head should not go
much above 30 inches, first, because high heads would, by bringing
extra weight upon the sand, make it too compact, and, second, because
when the pressure became too great the sediment layer on the surface of
the sand, in which most of the loss of head occurs, would no longer be
able to support the weight and, becoming broken, would allow the water
to pour through the comparatively large resulting openings at greatly
increased rates and with reduced efficiency.

In regard to the first point, a straight, even pressure many times
that of the water on the filter is incapable of compressing the sand.
It is much more the effect of the boots of the workmen when scraping
that makes the sand compact. I have found sand in natural banks at
Lawrence 70 or 80 feet below the surface, where it had been subjected
to corresponding pressure for thousands of years, to be quite as porous
as when packed in water in experimental filters in the usual way.

The second reason mentioned, or, as I may call it, the breaking-through
theory, is very generally if not universally accepted by German
engineers, and this is the reason for the low limit commonly adopted by
them.

A careful study of the results at Lawrence fails to show the slightest
deterioration of the effluents up to the limit used, 72 inches. Thus
in 1892, taking only the results of the continuous filters of full
height (Nos. 33A, 34A, 36A, and 37), we find that for the three days
before scraping, when the head was nearly 72 inches, the average
number of bacteria in the effluents was 31 per cc., while for the
three days after scraping, with very low heads, the number was 47. The
corresponding numbers of _B. prodigiosus_[17] were 1.1 and 2.7. This
shows better work with the highest heads, but is open to the objection
that the period just after scraping, owing to the disturbance of the
surface, is commonly supposed to be a period of low efficiency.

To avoid this criticism in calculating the corresponding results for
1893, the numbers of the bacteria for the intermediate days which could
not have been influenced either by scraping or by excessive head are
put side by side with the others. Taking these results as before for
continuous filters 72 inches high, and excluding those with extremely
fine sands and a filter which was only in operation a short time toward
the end of the year, we obtain the following results:

Water B.
Bacteria Prodigiosus
per cc. per cc.
Average 1st day after scraping, low heads 79 6.1
Average 2d day after scraping, low heads 44 4.1
Average 3d day after scraping, low heads 45 3.6
Intermediate days, medium heads 59 4.5
Second from last day, heads of nearly 72 inches 66 2.7
Next to the last day, heads of nearly 72 inches 56 3.2
Last day, heads of nearly 72 inches 83 2.5

These figures show a very slight increase of the water bacteria in the
effluent as the head approaches the limit, but no such increase as
might be expected from a breaking through of the sediment layer, and
the _B. prodigiosus_ which is believed to better indicate the removal
of the bacteria of the original water, actually shows a decrease, the
last day being the best day of the whole period.

The Lawrence results, then, uniformly and clearly point to a conclusion
directly opposite to the commonly accepted view, and I have thus
been led to examine somewhat closely the grounds upon which the
breaking-through theory rests.

The two works which have perhaps contributed most to the theories
of filtration are the Stralau and Altona works. After examining the
available records of these works, I am quite convinced that at these
places there has been, at times at least, decreased efficiency with
high heads. For the Stralau works this is well shown by Piefke’s
plates in the _Zeitschrift für Hygiene_, 1894, after page 188. In both
of these works, however, the apparatus (or lack of apparatus) for
regulating the rate is that shown by Fig. 5, page 49, and the rate
of filtration is thus dependent upon the rate of consumption and the
height of water in the reservoir. At the Stralau works, at the time
covered by the above-mentioned diagrams, the daily quantity of water
filtered was 27 times the capacity of the reservoir, and the rate
of filtration must consequently have adapted itself to the hourly
consumptions. The data which formed the basis of Kirkwood’s conclusions
are not given in detail, but it is quite safe to assume that they were
obtained from filters regulated as those at Altona and Stralau are
regulated, and what is said in regard to the latter will apply equally
to his results.

Piefke[18] shows that among the separate filters at Stralau, all
connected with the same pure-water reservoir, those connected through
the shorter pipes gave poorer effluents than the more remote filters,
and he attributes the difference to the frictional resistance of the
connecting pipes, which helped to prevent excessive rates in the
filters farthest away when the water in the reservoir became low, and
thus the fluctuations in the rates in these filters were less than in
those close to the reservoir. He

does not, however, notice, in speaking of the filters in which the
decreased efficiencies with high heads were specially marked, that they
follow in nearly the same order, and that of the four open filters
mentioned three were near the reservoir and only one was separated by
a comparatively long pipe, indicating that the deterioration with high
heads was only noticeable, or at least was much more conspicuous, in
those filters where the rates fluctuated most violently.

It requires no elaborate calculation to show that of two filters
connected with the same pure-water reservoir, as shown by Fig. 5,
with only simple gates on the connecting pipes, one of them clean and
throttled by a nearly closed gate, so that the normal pressure behind
the gate is above the highest level of water in the reservoir, and the
other clogged so that the normal pressure of the water in the drain is
considerably below the highest level of the water in the reservoir,
the latter will suffer much the more severe shocks with fluctuating
water-levels; and the fact being admitted that fluctuating levels are
unfavorable, we must go farther and conclude that the detrimental
action will increase with increasing loss of head. I am inclined to
think that this theory is adequate to explain the Stralau and Altona
results without resource to the breaking-through theory.

While the above does not at all prove the breaking-through theory to be
false, it explains the results upon which it rests in another way, and
can hardly fail to throw so much doubt upon it as to make us refuse to
allow its application to those works where a regular rate of filtration
is maintained regardless of variations in the consumption, until proof
is furnished that it is applicable to them.

I have been totally unable to find satisfactory European results in
regard to this point. The English works can furnish nothing, both on
account of the lack of regulating appliances and because the monthly
bacterial examinations are inadequate for a discussion of hourly or
daily changes. The results from the older Continental works are also
excluded for one or the other, or more often for both, of the above
reasons. The Hamburg, Tegel, and Müggel results, so far as they go,
show no deterioration with increased heads, but the heads are limited
to 24 or 28 inches by the construction of the filters, and the results
thus entirely fail to show what would be obtained with heads more than
twice as high.

I am thus forced to conclude that there is no adequate evidence of
inferior efficiency with high heads in filters where the rates are
independent of the water-level in the pure-water reservoir, the
only results directly to the point—the Lawrence results mentioned
above—indicating that the full efficiency is maintained with heads
reaching at least 72 inches.

The principal reason for desiring to allow a considerable loss of head
is an economical one; the period will then be lengthened, while the
frequency of scraping and the volume of sand to be washed and replaced
will be correspondingly reduced. There may be other advantages in long
periods, such as less trouble with scraping and better work in cold
winter weather, but the cost is the most important consideration.

It is the prevalent idea among the German engineers that the loss of
head after reaching 24 to 30 inches would increase very rapidly, so
that the quantity of water filtered, in case a much higher head was
allowed, would not be materially increased. No careful investigations,
however, have been made, and indeed they are hardly possible with
existing arrangements, as in the older filters the loss of head
fluctuates with varying rates of filtration in such a way that only
results of very doubtful value can be obtained, and in the newer works
the loss of head is too closely limited, and the curves which can be
drawn by extrapolation are evidently no safe indications of what would
actually happen if the process was carried farther.

On the other hand, I was told by the attendant at Darlington, England,
that since the building of the weir a few years ago, which now limits
the loss of head to about 18 inches instead of the 5 feet or more
formerly used, the quantity of sand to be removed has been three times
as great as formerly. No records are kept, and this can only be given
as the general impression of the man who superintends the work.

At Lawrence the average quantities of water filtered between scrapings
with sand of an effective size of 0.20 mm. have been as follows:

Maximum Loss of Million Gallons per Acre filtered
Head. between Scrapings.

1892. 1893. Average.

70 inches 58 88 73
34 foot 32 22 27
22 foot 17 16 16

With sand of an effective size of 0.29 mm. the results were:

1893.

70 inches 70
22 foot 29

These results indicate a great increase in the quantity of water
filtered between scrapings with increasing heads, the figures being
nearly proportional to the maximum heads used in the respective
cases. It is, of course, quite possible that the results would differ
in different places with the character of the raw water and of the
filtering material.

The depth of sand to be removed by scraping at one time is, within
limits, practically independent of the quantity of dirt which it has
accumulated, and any lengthening of the period means a corresponding
reduction in the quantity of sand to be removed, washed and replaced
and consequently an important reduction in the operating cost, as well
as a reduction in the area of filters out of use while being cleaned,
and so, in the capital cost.

Among the minor objections to an increased loss of head are the
greater head against which the water must be pumped, and the possible
increased difficulty of filling filters with filtered water from below
after scraping, but these would hardly have much weight against the
economy indicated by the Lawrence experiments for the higher heads.

High heads will also drive an increased quantity of water through any
cracks or passages in the filter. Such leaks have at last been found to
be the cause of the inferior work of the covered filters at Stralau,
the water going down unfiltered in certain corners, especially at high
heads; but with careful construction there should be no cracks, and
with the aid of bacteriology to find the possible leaks this ought not
to be a valid objection.

In conclusion: the trend of opinion is strongly in favor of limiting
the loss of head to about 24 to 30 inches as was suggested by Kirkwood,
but I am forced to conclude that there is reason to believe that
equally good results can be obtained with lower operating expenses by
allowing higher heads to be used, at least in the case of filters with
modern regulating appliances, and, I would suggest that filters should
be built so as not to exclude the use of moderately high heads, and
that the limit to be permanently used should be determined by actual
tests of efficiency and length of period with various losses of head
after starting the works.

CHAPTER V.

CLEANING FILTERS.

When a filter has become so far clogged that it will no longer pass
a satisfactory quantity of water with the allowable head it must be
cleaned by scraping off and removing the upper layer of dirty sand.

To do this without unnecessary loss of time the unfiltered water
standing upon the filter is removed by a drain above the sand provided
for that purpose. The water in the sand must then be lowered below the
surface of the sand by drawing water from the underdrains until the
sand is firm enough to bear the weight of the workmen. By the time
that this is accomplished the last water on the surface should have
soaked away, and the filter is ready to be scraped. This is done by
workmen with wide, sharp shovels, and the sand removed is taken to
the sand-washing apparatus to be washed and used again. Special pains
are given to securing rapid and cheap transportation of the sand. In
some cases it is wheeled out of the filter on an inclined plane to the
washer. In other cases a movable crane is provided which lifts the sand
in special receptacles and allows it to fall into cars on a tram-line
on which the crane also moves. The cars as filled are run to the washer
and also serve to bring back the washed sand. When the dirty sand has
been removed, the surface of the sand is carefully smoothed and raked.
This is especially necessary to remove the effects of the workmen’s
boots.

It is customary in the most carefully managed works to fill the sand
with filtered water from below, introduced through the underdrains. In
case the ordinary level of the water in the pure-water canal is higher
than the surface of the sand in the filters, this is accomplished
by simply opening a gate provided for the purpose, which allows the
water to pass around the regulating apparatus. Otherwise filters can
be filled from a special pipe taking its water from any filter which
at that time can deliver its effluent high enough for that purpose.
The quantity of water required for filling the sand from below is
ordinarily but a fraction of one per cent of the quantity filtered.

Formerly, instead of filling from below, after cleaning, the raw water
was brought directly onto the surface of the filter. This was said to
only imperfectly fill the sand-pores, which still contained much air.
If, however, the water is not brought on too rapidly it will sink into
the sand near the point where it is applied, pass laterally through the
sand or underlying gravel to other parts of the filter, and then rise,
so that even in this case all but a little of the filter will be really
filled from below. This is, however, open to the objection that however
slowly the water is introduced, the sand which absorbs it around the
inlet filters it at a very high rate and presumably imperfectly, so
that the water in the underdrains at the start will be poor quality
and the sand around the inlet will be unduly clogged. The practice of
filling from below is therefore well founded.

As soon as the surface of the sand is covered with the water from
below, raw water is introduced from above, filling the filter to
the standard height, care being taken at first that no currents
are produced which might wash the surface of the sand. It has been
recommended by Piefke and others that this water should be allowed
to stand for a time up to twenty-four hours before starting the
filtration, to allow the formation of a sediment layer, and in some
places, especially at Berlin and the works of some of the London
companies, this is done; but varying importance is attached to the
procedure, and it is invariably omitted, so far as I can learn, when
the demand for water is heavy.

The depth of sand removed by scraping must at least equal the
depth of the discolored layer, but there is no sharp dividing line,
the impurities gradually decreasing from the surface downward.
Fig. 12 shows the relative number of bacteria found in the sand at
various depths in one of the Lawrence experimental filters, and is a
representative result, although the actual numbers vary at different
times. In general it may be said that the bulk of the sediment is
retained in the upper quarter inch, but it is desirable to remove also
the less dirty sand below and, in fact, it is apparently impossible
with the method of scraping in use to remove so thin a layer as one
fourth inch. Practically the depth to which sand is removed is stated
to be from 0.40 to 1.20 inch. Exact statistics are not easily obtained,
but I think that 2 centimeters or 0.79 inch may be safely taken as
about the average depth usually removed in European filters, and it is
this depth which is indicated on Fig. 12.

[Illustration: FIG. 12.—DIAGRAM SHOWING ACCUMULATION OF BACTERIA NEAR
THE SURFACE OF THE SAND.]

At the Lawrence Experiment Station, the depth removed is often much
less than this, and depends upon the size of grain of the sand
employed, the coarser sands requiring to be more deeply scraped than
the finer ones. The method of scraping, however, which allows the
removal of very thin sand layers, is only possible because of the
small size of the filters, and as it is incapable of application on a
large scale, the depths thus removed are only interesting as showing
the results which might be obtained in practice with a more perfect
method of scraping.

The replacing of the washed sand is usually delayed until the filter
has been scraped quite a number of times—commonly for a year. The last
scraping before refilling is much deeper than usual, because the sand
below the depth of the ordinary scraping is somewhat dirty, and might
cause trouble if left below the clean sand.

In England it is the usual if not the universal practice to replace the
washed sand at the bottom between the old sand and the gravel. This is
done by digging up the entire filter in sections about six feet wide.
The old sand in the first section is removed clear down to the gravel,
and the depth of washed sand which is to be replaced is put in its
place. The old sand from the next six-foot section is then shovelled
upon the first section of clean sand, and its place is in turn filled
with fresh sand. With this practice the workmen’s boots are likely to
disturb the gravel each year, necessitating a thicker layer of the
upper and finest grade than would otherwise be required.

In Germany this is also sometimes done, but more frequently the upper
layer of slightly clogged sand below the regular scraping is removed
as far as the slightest discoloration can be seen, perhaps 6 inches
deep. The sand below is loosened for another 6 inches and allowed to
stand dry, if possible, for some days; afterwards the washed sand is
brought on and placed above. The washed sand is never replaced without
some such treatment, because the slightly clogged sand below the layer
removed would act as if finer than the freshly washed sand,[19] and
there would be a tendency to sub-surface clogging.

FREQUENCY OF SCRAPING.

The frequency of scraping depends upon the character of the raw water,
the thoroughness of the preliminary sedimentation, the grain-size of
the filter sand, the rate of filtration, and the maximum loss of head
allowed. With suitable conditions the period between scrapings should
never be less than one week, and will but rarely exceed two months.
Under exceptional conditions, however, periods have been recorded as
low as one day and as high as one hundred and ten days. Periods of less
than a week’s duration are almost conclusive evidence that something
is radically wrong, and the periods of one day mentioned were actually
accompanied by very inadequate filtration. In 1892 the average periods
at the German works varied from 9.5 days at Stettin (with an excessive
rate) to 40 days at Brunswick, the average of all being 25 days.[20]

The quantity of water per acre filtered between scrapings forms the
most convenient basis for calculation. The effect of rate (page
49), loss of head (page 65), and size of sand grain (page 32) have
already been discussed, and it will suffice to say here that the total
quantity filtered between scrapings is apparently independent of the
rate of filtration, but varies with the maximum loss of head and with
the grain-size of the sand, and apparently nearly in proportion to
them. Eleven German filter-works in 1892, drawing their waters from
rivers, filtered on an average 51 million gallons of water per acre
between scrapings, the single results ranging from 28 at Bremen to 71
at Stuttgart, while Zürich, drawing its water from a lake which is
but very rarely turbid, filtered 260 million gallons per acre between
scrapings. Unfortunately, the quantities at Berlin, where (in 1892 two
thirds and now all) the water is drawn from comparatively large ponds
on the rivers, are not available for comparison.

At London, in 1884, the average quantities of water filtered

between scrapings varied from 43 to 136 million gallons per acre with
the different companies, averaging 85, and in 1892 the quantities
ranged from 73 to 157, averaging 90 million gallons per acre. The
greater quantity filtered at London may be due to the greater sizes of
the sedimentation-basins, which for all the companies together hold a
nine days’ supply at London against probably less than one day’s supply
for the German works.

There is little information available in regard to the frequency
of scraping with water drawn from impounding reservoirs. In some
experiments made by Mr. FitzGerald at the Chestnut Hill reservoir,
Boston, the results of which are as yet unpublished, a filter with
sand of an effective size of only .09 mm. averaged 58 million gallons
per acre between scrapings for nine periods, the rate of filtration
being 1.50 million gallons per acre daily, while another filter, with
sand of an effective size of .18 mm., passed an average of 93 million
gallons per acre for ten periods at the same rate. These experiments
extended through all seasons of the year, and taking into account the
comparative fineness of the sands they show rather high quantities of
water filtered between scrapings.

The quantity of water filtered between scrapings is usually greatest
in winter, owing to the smaller quantity of sediment in the raw water
at this season, and is lowest in times of flood, regardless of season.
In summer the quantity is often reduced to a very low figure in waters
supporting algæ growths, especially when the filters are not covered.
Thus at Stralau in 1893 during the algæ period the quantity was reduced
to 14 million gallons per acre for open filters,[21] but this was quite
exceptional, the much-polluted, though comparatively clear, Spree water
furnishing unusually favorable conditions for the algæ.

QUANTITY OF SAND TO BE REMOVED.

In regard to the quantity of sand to be removed and washed, if we
take the average result given above for the German works filtering
river-waters of 51,000,000 gallons per acre filtered between scrapings,
and the depth of sand removed at two centimeters or 0.79 inch, we
find that one volume of sand is required for every 2375 volumes of
water filtered, or 2.10 cubic yards per million gallons. At Bremen,
the highest average result, the quantity would be 3.80 yards, and at
Stralau during the algæ season 7.70 yards. At Zürich, on the other
hand, the quantity is only 0.41 yard, and at London, with 87,000,000
gallons per acre filtered between scrapings, the quantity of sand
washed would be 1.24 yards per million gallons; assuming always that
the layer removed is 0.79 inch thick.

These estimates are for the regular scrapings only, and do not include
the annual deeper scraping before replacing the sand, which would
increase them by about one third.

WASTING THE EFFLUENTS AFTER SCRAPING.

It has already been stated that an important part of the filtration
takes place in the sediment layer deposited on top of the sand from
the water. When this layer is removed by scraping its influence is
temporarily removed, and reduced efficiency of filtration may result.
The significance of this reduced efficiency became apparent when the
bacteria in the water were studied in their relations to disease, and
Piefke suggested[22] that the first effluent after scraping should
be rejected for one day after ordinary scrapings and for one week
after replacing the sand. In a more recent paper[23] he reduces these
estimates to the first million gallons of water per acre filtered after
scraping

for open and twice as great a quantity for covered filters, and to six
days after replacing the sand, which last he estimates will occur only
once a year. Taking the quantity of water filtered between scrapings at
13.9 million gallons per acre, the quantity observed at Stralau in the
summer of 1893, he finds that it is necessary to waste 9 per cent of
the total quantity of effluent from open and 13.8 per cent of that from
covered filters.

The eleven German water-works[24] filtering river-waters, however,
filtered on an average 51.0 instead of 13.9 million gallons per acre
between scrapings, and applying Piefke’s figures to them the quantities
of water to be wasted would be only about one fourth of his estimates
for Stralau.

The rules of the Imperial Board of Health[25] require that every German
filter shall be so constructed “that when an inferior effluent results
it can be disconnected from the pure-water pipes and the filtrate
allowed to be wasted.” The drain-pipe for removing the rejected water
should be connected below the apparatus for regulating the rate and
loss of head, so that the filter can be operated exactly as usual,
and the effluent can be turned back to the pure-water pipes without
stopping or changing the rate. The works at Berlin and at Hamburg
conform to this requirement, and most of the older German works have
been or are being built over to make them do so.

In regard to the extent of deterioration after scraping, Piefke’s
experiments have always shown much larger numbers of bacteria both of
the ordinary forms and of special applied forms on the first day after
scraping, the numbers frequently being many times as high as at other
times.

At the Lawrence Experiment Station it was found in 1892 that on an
average the number of water bacteria was increased by 70 per cent
(continuous filters only) for the three days following scraping, while
_B. prodigiosus_ when applied was increased 140 per

cent, the increase being most marked where the depth of sand was
least, and with the highest rate of filtration.

The same tendency was found in 1893, when the increase in the water
bacteria on the first day after scraping was only 19 per cent and _B.
prodigiosus_ 64 per cent, but for a portion of the year the difference
was greater, averaging 132 and 262 per cent, respectively. These
differences are much less than those recorded by Piefke, and with the
high efficiencies regularly obtained at Lawrence they would hardly
justify the expensive practice of wasting the effluent.

The reduction in efficiency following scraping is much less at low
rates, and if a filter is started at much less than its normal rate
after scraping, and then gradually increased to the standard after
the sediment layer is formed, the poor work will be largely avoided.
Practically this is done at Berlin and at Hamburg. The filters are
started at a fourth or less of the usual rates and are gradually
increased, as past experience with bacterial results has shown it can
be safely done, and the effluent is then even at first so well purified
that it need not be wasted.

Practically in building new filters the provision of a suitable
connection for wasting the effluents into the drain which is necessary
for emptying them involves no serious expense and should be provided,
but it may be questioned how often it should be used for wasting the
effluents. If the raw water is so bad that a good effluent cannot be
obtained by careful manipulation even just after scraping, the course
of the Berlin authorities in closing the Stralau works and seeking a
less polluted supply would seem to be the only really safe procedure.

SAND-WASHING.

[Illustration: CLEANING A FILTER, EAST LONDON.]

[Illustration: WASHING DIRTY SAND WITH HOSE, ANTWERP.]

[_To face page 76._]

The sand-washing apparatus is an important part of most European
filtering plants. It seldom happens that a natural sand can be found
clean enough and sufficiently free from fine particles although such
a sand was found and used for the Lawrence filter. Most of the sand in
use for filtration in Europe was originally washed. In the operation of
the filters also, sand-washing is used for the dirty sand, which can
then be used over and over at a much lower cost than would be the case
if fresh sand was used for refilling. The methods used for washing sand
at the different works present a great variety both in their details
and in the underlying principles. Formerly boxes with double perforated
bottoms in which the sand was placed and stirred by a man as water from
below rose through them, and other similar arrangements were commonly
used, but they are at present only retained, so far as I know, in some
of the smaller English works. The cleansing obtained is apparently
considerably less thorough than with some of the modern devices.

[Illustration: FIG. 13.—HOSE-WASHING FOR DIRTY SAND.]

Hose-washing is used in London by the Southwark and Vauxhall, Lambeth
and Chelsea companies, and also at Antwerp. For this a platform is
constructed about 15 feet long by 8 feet wide, with a pitch lengthwise
of 6 to 8 inches (Fig. 13). The platform is surrounded by a wall
rising from one foot at the bottom to three feet high at the top,
except the lower end, which is closed by a removable plank weir 5 or 6
inches high. From two to four cubic yards of the sand are placed upon
this platform and a stream of water from a hose with a 3/4 or 7/8-inch
nozzle is played upon it, moving it about from place to place. The sand
itself is always kept toward the upper end of the platform, while the
water with the dirt removed flows down into the pond made by the weir,
where the sand settles out and the dirt overflows with the water. When
the water comes off clear, which is usually after an hour or a little
less, the weir is removed, and, after draining, the sand is removed.
These arrangements are built in pairs so that the hose can be used in
one while the sand is being changed in the other. They are usually
built of brick laid in cement, but plank and iron are also used. The
corners are sometimes carried out square as in the figure, but are more
often rounded. The washing is apparently fairly well done.

In Germany the so-called “drum” washing-machine, drawings of which have
been several times published,[26] has come to be almost universally
used. It consists of a large revolving cylinder, on the bottom of the
inside of which the sand is slowly pushed up toward the higher end by
endless screw-blades attached to the cylinder, while water is freely
played upon it all the way. The machine requires a special house for
its accommodation and from 2 to 4 horse-power for its operation. It
washes from 2.5 to 4 yards of sand per hour most thoroughly, with a
consumption of from 11 to 14 times as large a volume of water. The
apparatus is not patented or made for sale, but full plans can be
easily secured.

A machine made by Samuel Pegg & Sons, Leicester, Eng., pushes the
sand up a slight incline down which water flows. It is very heavy and
requires power to operate it. The patent has

expired. A machine much like it but lighter and more convenient and
moved by water-power derived from the water used for washing instead of
steam-power is used at Zürich with good results.

In Greenway’s machine the sand is forced by a screw through a long
narrow cylinder in which there is a current of water in the opposite
direction. The power required is furnished by a water-motor, as with
the machine at Zürich. The apparatus is mounted on wheels and is
portable; it has an appliance for piling up the washed sand or loading
it onto cars. It is patented and is manufactured by James Gibb & Co.,
London.

Several of the London water companies are now using ejector washers,
and such an apparatus has been placed by the side of the “drum” washers
at Hamburg. This apparatus was made by Körting Brothers in Hannover,
and combines the ejectors long made by that firm with hoppers from
designs by Mr. Bryan, engineer of the East London Water Company. An
apparatus differing from this only in the shape of the ejectors and
some minor details has been patented in England, and is for sale by
Messrs. Hunter, Frazer & Goodman, Bow, London.

Both of these forms consist of a series of conical hoppers, from the
bottom of each of which the sand and water are forced into the top of
the next by means of ejectors, the excess of dirty water overflowing
from the top of each hopper. The apparatus is compact and not likely
to get out of order, but is not portable. It can be easily arranged to
take the sand at the level of the ground, or even lower if desired, and
deliver it washed at some little elevation, thus minimizing hand-labor.
The washing is regular and thorough. The objection most frequently
raised against its use is the quantity of water required, but at
Hamburg I was informed that the volume of water required was only about
15 times that of the sand, while almost as much (13-14 volumes) were
required for the “drum” washers, and the saving in power much more
than offset the extra cost for water.

In addition to the above processes of sand-washing, Piefke’s method
of cleaning without scraping[27] might be mentioned, although as
yet it has hardly passed the experimental stage, and has only been
used on extremely small filters. The process consists of stirring
the surface sand of the filter with “waltzers” while a thin sheet of
water rapidly flows over the surface. This arrangement necessitates a
special construction of the filters, providing for rapidly removing
the unfiltered water from the surface, and for producing a regular and
rapid movement of a thin sheet of water over the surface. In the little
filters now in use, one of which I saw in a brewery in Berlin, the
cleaning is rapidly, cheaply, and apparently well done.

In washing dirty sand it is obvious that any small sand-grains will
be removed with the dirt, and in washing new sand the main object is
to remove the grains below a certain size. It is also apparent that
the sizes of grains which will and those which will not be removed
are dependent upon the mechanical arrangements of the washer, as, for
example, with the ejectors, upon the sizes of the hoppers, and the
quantity of water passing through them, and care should be taken to
make them correspond with the size of grain selected for the filter
sand. This can only be done by experiment, as no results are available
on this point.

In some places filtered water is used for sand-washing, although this
seems quite unnecessary, as ordinary river-water answers very well.
It is, however, often cheaper, especially in small works, to use the
filtered water from the mains rather than provide a separate supply for
the washers.

The quantity of water required for washing may be estimated at 15 times
the volume of the sand and the sand as 0.04 per cent of the volume of
the water filtered (page 74), so that

0.6 per cent of the total quantity of water filtered will be required
for sand-washing.

The cost of sand-washing in Germany with the “drum” washers is said
to be from 14 to 20 cents per cubic yard, including labor, power, and
water. In America the water would cost no more, but the labor would be
perhaps twice as dear. With an ejector apparatus I should estimate the
cost of washing dirty sand as follows: The sand would be brought and
dumped near to the washer, and one man could easily feed it in, as no
lifting is required. Two men would probably be required to shovel the
washed sand into barrows or carts with the present arrangements, but I
think with a little ingenuity this handling could be made easier.

ESTIMATED COST OF OPERATING EJECTOR WASHERS 9 HOURS.

Wages of 3 men at $2.00 $6.00
110,000 gals, water (15 times the volume of sand)
at 0.05 a thousand gals. 5.50
-----
Total cost of washing 36 cubic yards $11.50
or 32 cents a cubic yard.

The cost of washing new sand might be somewhat less. The other costs of
cleaning filters, scraping, transporting, and replacing the sand are
much greater than the washing itself. Lindley states that at Warsaw 29
days’ labor of 10 hours for one man are required to scrape an acre of
filter surface, and four times as much for the annual deep scraping,
digging up, and replacing the sand. The first expense occurs in general
monthly, and the second only once a year. At other places where I have
secured corresponding data the figures range from 19 to 40 days’ labor
to scrape one acre, and average about the same as Lindley estimates.

Under some conditions sand-washing does not pay, and in still others
it is almost impossible. No apparatus has yet been devised which will
wash the dirt out of the fine dune-sands used in Holland without
washing a large part of the sand itself away, and in these works fresh
sand, which is available in unlimited quantities and close to the
works, is always used. At Breslau the dirty sand is sold for building
purposes for one third of the price paid for new sand dredged from the
river, delivered at the works, and no sand is ever washed. Budapest,
Warsaw, and Rotterdam also use fresh river-sand without washing, except
a very crude washing to remove clay at Budapest.

CHAPTER VI.

THEORY AND EFFICIENCY OF CONTINUOUS FILTRATION.

The first filters for a public water-supply were built by James
Simpson, engineer of the Chelsea Water Company at London in 1829. They
were apparently intended to remove dirt from the water in imitation
of natural processes, and without any very clear conception of either
the exact extent of purification or the way in which it was to be
accomplished. The removal of turbidity was the most obvious result, and
a clear effluent was the single test of the efficiency of filtration,
as it remains the legal criterion of the work of the London filters
even to-day, notwithstanding the discovery and use of other and more
delicate tests.

The invention and use of methods for determining the organic matters
in water by Wanklyn and Frankland, about 1870, led to the discovery
that the proportion of organic matters removed by filtration was
disappointingly low, and as, at the time, and for many years afterward,
an exaggerated importance was given to the mere quantities of organic
matters in water, it was concluded that filtration had only a limited
influence upon the healthfulness of the filtered water, and that
practically as much care must be given to securing an unpolluted water
as would be the case if it were delivered direct without filtration.
This theory, although not confirmed by more recent investigation,
undoubtedly has had a good influence upon the English works by causing
the selection of raw waters free from excessive pollutions, and, in
cases like the London supplies, drawn from the Thames and the Lea, in
stimulating a most jealous care of the watersheds and the purification
of sewage by the towns upon them.

It was only after the discovery of the bacteria in water and their
relations to health that the hygenic significance of filtration
commenced to be really understood. Investigations of the bacteria in
the waters before and after filtration were carried out at Berlin
by Plagge and Proskauer, at London by Dr. Percy Frankland, and also
at Zürich, Altona, and on a smaller scale at other places. These
investigations showed that the bacteria were mainly removed by
filtration, the numbers in the effluents rarely exceeding two or three
per cent of those in the raw water. This gave a new aspect to the
problem.

It was further observed, especially at Berlin and Zürich, that the
numbers of bacteria in effluents were apparently quite independent
of the numbers in the raw water, and the theory was formed that all
of the bacteria were stopped by the filters, and that those found in
the effluents were the result of contamination from the air and of
growths in the underdrains. The logical conclusion from this theory was
that filtered water was quite suitable for drinking regardless of the
pollution of its source.

It was, however, found that the numbers of bacteria in the effluents
were higher immediately after scraping than at other times, and it was
concluded that before the formation of the sediment layer some bacteria
were able to pass the sand, and it was therefore recommended that the
first water filtered after scraping should be rejected.

Piefke at Berlin gave the subject careful study, and came to the
conclusion that it was almost entirely the sediment layer which
stopped the bacteria, and that the bacteria themselves in the sediment
layer formed a slimy mass which completely intercepted those in the
passing water. When this layer was removed by scraping, the action
was stopped until a new crop of bacteria had accumulated. In support
of this idea he stated that he had taken ordinary good filter-sand
and killed the bacteria in it by heating it, and that on passing
water through, no purification was effected—in fact, the effluent
contained more bacteria than the raw water. After a little, bacteria
established themselves in the sand, and then the usual purification
was obtained. Piefke concluded that the action of the filter was a
biological one; that simple straining was quite inadequate to produce
the results obtained; that the action of the filter was mainly confined
to the sediment layer, and that the depth of sand beyond the slight
depth necessary for the support of this layer had no appreciable
influence upon the results. The effect of this theory is still seen in
the shallow sand layers used at Berlin and some other German works,
although at London the tendency is rather toward thicker sand layers.

Piefke’s deductions, however, are not entirely supported by his data
as we understand them in the light of more recent investigation.
The experiment with sterilized sand has been repeatedly tried at
the Lawrence Experiment Station with results which quite agree with
Piefke’s, but it has also been found that the high numbers, often many
times as high as in the raw water, do not represent bacteria which pass
in the ordinary course of filtration, but instead enormous growths of
bacteria throughout the sand supported by the cooked organic matter in
it. It has been repeatedly found that ordinary sand quite incapable of
supporting bacterial growths, after heating to a temperature capable
of killing the bacteria will afterwards furnish the food for most
extraordinary numbers. A filter of such sand may stop the bacteria of
the passing water quite as effectually as any other filter, but if so,
the fact cannot be determined without recourse to special methods, on
account of the enormous numbers of bacteria in the sand, a small part
of which are carried forward by the passing water, and completely mask
the normal action of the filter.

The theory that all or practically all of the bacteria are intercepted
by the sediment layer, and that those in the effluent are the result
of growths in the sand or underdrains, received two hard blows in 1889
and 1891, when mild epidemics of typhoid fever followed unusually
high numbers of bacteria in the effluents at Altona and at Stralau in
Berlin, with good evidence in each case that the fever was directly due
to the water. Both of these cases came during, and as the result of,
severe winter weather with open filters and under conditions which are
now recognized as extremely unfavorable for good filtration.

As a result of the first of these epidemics a series of experiments
were made at Stralau by Fränkel and Piefke in 1890. Small filters were
constructed, and water passed exactly as in the ordinary filters.
Bacteria of special kinds not existing in the raw water or effluents
were then applied, and the presence of a very small fraction of them
in the effluents demonstrated beyond a doubt that they had passed
through the filters under the ordinary conditions of filtration. These
experiments were afterwards repeated by Piefke alone under somewhat
different conditions with similar results. The numbers of bacteria
passing, although large enough to establish the point that some do
pass, were nevertheless in general but a small fraction of one per cent
of the many thousands applied.

This method of testing the efficiency of filters had already been
used quite independently by Prof. Sedgwick at the Lawrence Experiment
Station in connection with the purification of sewage, and has since
been extensively used there for experiments with water-filtration.

Kümmel also found at Altona that while in the regular samples for
bacterial examination, all taken at the same time in the day, there
was no apparent connection between the numbers of bacteria in the raw
water and effluents, by taking samples at frequent intervals throughout
the twenty-four hours, as has been done in a more recent series of
experiments, and allowing for the time required for the water to pass
the filters, a well-marked connection was found to exist between the
numbers of bacteria in the raw water and in the effluents.

[Illustration: FIG. 14.—SHOWING BACTERIA SUPPOSED TO COME THROUGH
FILTERS AND FROM THE UNDERDRAINS.]

The subject has more recently been studied in much detail at the
Lawrence Experiment Station, and it now appears that the bacteria
in the effluent from a filter are from two sources: directly from
the filtered water, and from the lower layers of the filter and
underdrains. Thus we may say:

Bacteria in effluent = Bacteria from underdrains + _a_/100 × bacteria
in raw water,

where _a_ is the per cent of bacteria actually passing the filter.

Both of these terms depend upon a whole series of complex and but
imperfectly understood conditions. In general the bacteria from the
underdrains are low in cold winter weather, often almost _nil_, while
at Lawrence with water temperatures of 70 to 75 degrees, and over, in
July and August, the numbers from this source may reach 200 or 300,
but for the other ten months of the year rarely exceed 50 under normal
conditions. In summer especially it seems to be greater at low than
at high rates of filtration (although a high rate for a short time
only increases it), and so varies in the opposite way from the numbers
actually passing the filters. This subject is by no means clearly
understood; it is difficult, almost impossible, to separate the numbers
of bacteria into the two parts—those which come directly through and
may be dangerous, and those which have other origins and are harmless.
The sketch, Fig. 14, is drawn to represent my idea of the way they may
be divided. It has no statistical basis whatever. The light unshaded
section shows the percentage number of bacteria which I conceive to
be coming through a filter under given conditions at various rates of
filtration, while the shaded section above represents the bacteria from
other sources, and the upper line represents the sum of the two, or
the total number of bacteria in the effluent. The relative importance
of the two parts would probably vary widely with various conditions.
With the conditions indicated by the sketch the number of bacteria in
the effluent is almost constant: for a variation of only from 1.4 to
2.5 per cent of the number applied for the whole range is not a wide
fluctuation for bacterial results, but the number in the lower and
dangerous section is always rapidly increasing with increasing rate.

This theory of filtration accounts for many otherwise perplexing facts.
The conclusion reached at Zürich and elsewhere that the efficiency of
filtration is independent of rate may be explained in this way. This is
especially probable at Zürich, where the number of bacteria in the raw
water was only about 200, and an extremely large proportion relatively
would have to pass to make a well-marked impression upon the total
number in the effluent.

These underdrain bacteria are, so far as we know, entirely harmless;
we are only interested in them to determine how far they are capable
of decreasing the apparent efficiency of filtration below the actual
efficiency, or the per cent of bacteria really removed by the filter.

This efficiency is dependent upon a large number of conditions many
of which have already been discussed in connection with grain-size
of filter sand, underdrains, rate of filtration, loss of head, etc.,
and a mere reference to them here will suffice. Perhaps the most
important single condition is the rate, the numbers of bacteria passing
increase rapidly with it. Next, fine sand and in moderately deep
layers tends to give high efficiency. The influence of the loss of
head, often mentioned, is not shown to be important by the Lawrence
results, nor can I find satisfactory European results in support of
it. Uniformity in the rate of filtration on all parts of the filtering
area and a constant rate throughout the twenty-four hours are regarded
as essential conditions for the best results. Severe winter weather
has indirectly, by disturbing the regular action of open filters, an
injurious influence, and has been the cause of most of the cases where
filtered waters have been known to injure the health of those who have
drunk them. This action is excluded in filters covered with masonry
arches and soil, and such construction is apparently necessary for the
best results in places subject to cold winters.

The efficiency of filtration under various conditions has been studied
by a most elaborate series of experiments at Lawrence with small
filters to which water has been applied containing a bacterium (_B.
prodigiosus_) which does not occur naturally in this country and is
not capable of growing in the filter, so that the results should
represent only the bacteria coming through the filter and not include
any additions from the underdrains. These results, which have been
published in full in the reports of the Massachusetts State Board of
Health, especially for the years 1892 and 1893, show that the number
of bacteria passing increases rapidly with increasing rate, and slowly
with decreasing sand thickness and increased size of sand-grain.

Assuming that the number of bacteria passing is expressed by the formula

1 [(rate)^2 × effective size of sand]
Per cent bacteria passing = — ————————————————————————————————————————
2 ([sqrt](thickness of the sand in inches))

where the rate is expressed in million gallons per acre daily, and
calculating by it the numbers of bacteria for the seventy-three months
for which satisfactory data are available from 11 filters in 1892 and
1893, we find that

In 14 cases the numbers observed were 4 to 9 times as great as the
calculated numbers;

In 6 cases they were 2 to 3 times as great;

In 35 cases they were between 1/2 and 2 times the calculated numbers.

In 17 cases they were 1/2 to 1/3 of them.

In 11 cases they were less than 1/3 the calculated numbers.

The agreement is only moderately good, and in fact no such formula
could be expected to give more than very rough approximations, because
it does not take into consideration the numerous other elements, such
as uniformity and regularity of filtration, the influence of scraping,
the character of the sediment in the raw water, etc., which are known
to affect the results. Perhaps the most marked general difference is
the tendency of new or freshly-filled filters to give higher, and
of old and well-compacted filters to give lower, results than those
indicated by the formula.

Comparing this formula with Piefke’s results given in his “Neue
Ermittelungen”[28] the formula gives in the first series (0.34 mm.
sand, 0.50 m. thick, and rate 100 mm. per hour), 0.25 per cent passing,
while the average number of _B. violacious_ reported, excluding the
first day of decreased efficiency after scraping, was 0.26 per cent. In
the second series, with half as high a rate the numbers checked exactly
the calculated 0.06 per cent.

In other experiments,[29] however, in 1893, when the calculated per
cent was also 0.25, only 0.03, 0.04, and 0.07 per cent were observed in
the effluents.

Comparing the results from the actual filters, (which numbers also
include the bacteria from the underdrains and should therefore be
somewhat higher) with the numbers calculated as passing through,
I find that for the 46 days, Aug. 20 to Oct. 4, 1893, for which
detailed results of the Stralau works are given by Piefke, the average
calculated number passing is 0.20 per

cent, while twice as many were observed in the effluents; although
three of the filters gave better effluents than the other eight, and
the numbers from them approximated closely the calculated numbers. If
we calculate the percentages of bacteria passing a number of filters,
using the maximum rate of filtration allowed for the German filters
where this is accurately determined, and for the English filters
taking the maximum rate at one and one-half times the rate obtained by
dividing the daily quantity by the area of filters actually in use, we
obtain:

----------------------+--------+---------+-----------+--------------
|Average |Effective| Maximum | Per cent
|Depth of| Size of | Rate of | Bacteria
| Sand, | Sand- |Filtration.| passing
| Inches.| grain. | | 1 r^2d
| | | |= - ----------
| | | | 2 [sqrt]sand
----------------------+--------+---------+-----------+--------------
Hamburg | 32 | 0.31 | 1.60 | 0.07
Altona | 28 | 0.34 | 2.57 | 0.21
Berlin, Stralau | 20 | 0.34 | 2.57 | 0.25
Berlin, Müggel | 20 | 0.34 | 2.57 | 0.25
Berlin, Tegel | 20 | 0.37 | 2.57 | 0.27
London, Southwark & | | | |
Vauxhall | 36 | 0.34 | 2.81 | 0.22
London, West Middlesex| 39 | 0.37 | 2.81 | 0.23
London, Chelsea | 54 | 0.36 | 3.27 | 0.26
London, Grand Junction| 30 | 0.40 | 3.27 | 0.39
London, Lambeth | 36 | 0.36 | 3.75 | 0.42
Middlesborough | 20 | 0.42 | 5.85 | 1.58
Zürich | 26 | 0.35 | 7.50 | 1.90
----------------------+--------+---------+-----------+--------------

The numbers actually observed are in every case higher than the
calculated per cents passing, as indeed they should be on account of
those coming from the underdrains, accidental contamination of the
samples, etc.

It may be said that filtration now practised in European works under
ordinary conditions never allows over 1 or 2 per cent bacteria of the
raw water to pass, and ordinarily not over one fourth to one half
of one per cent, although exact data cannot be obtained owing to
masking effect of the bacteria which come from below and which bear
no relation to those of the raw water. By increasing the size of the
filters, fineness and depth of sand (as at Hamburg), the efficiency
can be materially increased above these figures. At the same time
it must be borne in mind that the effectiveness of a filter may be
greatly impaired by inadequate underdraining, by fluctuating rates of
filtration where these are allowed, by freezing in winter in the case
of open filters in cold climates, and by other irregularities, all of
which can be prevented by careful attention to the respective points.

The action of a continuous filter throughout is mainly that of an
exceedingly fine strainer, and like a strainer is mainly confined to
the suspended or insoluble matters in the raw water. The turbidity,
sediment, and bacteria of the raw water are largely or entirely
removed, while hardness, organic matter, and color, so far as they are
in solution, are removed to only a slight extent, if at all. Hardness
can be removed by the addition of lime in carefully determined quantity
before filtration (Clark’s process), by means of which the excess of
carbonic acid in the water is absorbed and the lime added, together
with that previously in the water, is precipitated.

Ordinary filtration will remove from one fourth to one third of the
yellow-brown color of peaty water. A larger proportion can be removed
by the addition of alum, which by decomposing forms an insoluble
compound of alumina with the coloring matter, while the acid of the
alum goes into the effluent either as free acid, or in combination with
the lime or other base in the water, according to their respective
quantities. Freshly precipitated alumina can be substituted for the
alum at increased expense and trouble, and tends to remove the color
without adding acid to the water. These will be discussed more in
detail in connection with mechanical filters. Alum is but rarely used
in slow sand filtration, the most important works where it is used
being in Holland with peaty waters.

After all, the most conclusive test of the efficiency of filtration is
the healthfulness of the people who drink the filtered water; and the
fact that many European cities take water-supplies from sources which
would not be considered fit for use in the United States and, after
filtering them, deliver them to populations having death-rates from
water-carried diseases which are so low as to be the objects of our
admiration, is the best proof of the efficiency of carefully conducted
filtration.

It is only necessary to refer to London, drawing its water from the
two small and polluted rivers, the Thames and the Lea; to Altona,
drawing its water from the Elbe, polluted by the sewage of 6,000,000
people, 700,000 of them within ten miles above the intakes; to Berlin,
using the waters of the Havel and the Spree; to Breslau, taking its
water from the Oder charged with the sewage of mining districts in
Silicia and Galicia, where cholera is so common; to Lawrence, with its
greatly decreased death-rate since it has had filtered water, and to
the hundred other places which protect themselves from the infectious
matters in their raw waters by means of filtration. A few of these
cases are described more in detail in Appendices V to IX, and many
others in the literature mentioned in Appendix X.

An adequate presentation of even those data which have been already
worked up and published would occupy too much space. I think every one
who has carefully studied the recent history of water filtration in
its relation to disease has been convinced that filtration carefully
executed under suitable and normal conditions, even if not an absolute,
is at least a very substantial protection against water-carried
diseases, and the few apparent failures to remove objectionable
qualities have been without exception due to abnormal conditions which
are now understood and in future can be prevented.

BACTERIAL EXAMINATION OF WATERS.

Every large filter-plant should have arrangements for the systematic
bacterial examination of the water before and after filtration,
especially where the raw water is subject to serious pollution. Such
examinations need not be excessively expensive, and they will not
only show the efficiency of the plant as a whole, but may be made to
show the relative efficiencies of the separate filters, the relative
efficiencies at different parts of the periods of operation, the effect
of cold weather, etc., and will then be a substantial aid to the
superintendent in always securing good effluents at the minimum cost.

In addition a complete record of the bacteria in the water at different
times may aid in determining definitely whether the water was connected
with outbreaks of disease. Thus if an outbreak of disease of any
kind were preceded at a certain interval by a great increase in the
number of bacteria,—as has been the case, for example, with the
typhoid epidemics at Altona and Berlin (see Appendices II and VII),—a
presumption would arise that they might have been connected with
each other, and each time it was repeated the presumption would be
strengthened, while, on the other hand, outbreaks occurring while the
bacteria remained constantly low would tend to discredit such a theory.

Bacterial investigations inaugurated after an epidemic is recognized,
as has frequently been done, seldom lead to results of value, both
because the local normal bacterial conditions are generally unknown at
the commencement of the investigation, and because the most important
time, the time of infection, is already long past before the first
samples are taken. The fact that such sporadic activities have led
to few definite results should throw no discredit upon continued
observations, which have repeatedly proved of inestimable value.

Considerable misconception of the use of bacterial examinations
exists. The simple bacterial count ordinarily used, and of which I
am now speaking, does not and cannot show whether a water contains
disease-germs or not. I object to the Chicago water, not so much
because a glass of it contains a hundred thousand bacteria more
or less, as because I am convinced, by a study of its source in
connection with the city’s death-rate, that it actually carries
disease-germs which prove injurious to thousands of those who drink
it. Now the fact being admitted that the water is injurious to health,
variations in the numbers of bacteria in the water drawn from different
intakes and at different times probably correspond roughly with varying
proportions of fresh sewage, and indicate roughly the relative dangers
from the use of the respective waters. If filters should be introduced,
the numbers of bacteria in the effluents under various conditions would
be an index of the respective efficiencies of filtration, and would
serve to detect poor work, and would probably suggest the measures
necessary for better results.

I would suggest the desirability of such investigations where
mechanical filters are used, quite as much as in connection with
slow filtration; and it would also be most desirable in the case of
many water-supplies which are not filtered at all. Such continued
observations have been made at Berlin since 1884; at London since 1886;
at Boston and Lawrence since 1888; and recently at a large number
of places, including Chicago, where observations by the city were
commenced in 1894. They are now required by the German Government in
the case of all filtered public water-supplies in Germany, without
regard to the source of the raw water. The German standard requires
that the effluent from each single filter, as well as the mix…

source: Project Gutenberglicence: Public domain (per item)year: —id: 69025citation: https://www.gutenberg.org/ebooks/69025characters: 200,001

record · JSON · record JSON

Related services and records

Services

  • Estate — measured countries, lanes and facts
  • Intel — live corroborated events
  • Legal — statutes, cases and citations
  • Encyclopedia — articles with inline sources
  • Space — launches, satellites and orbits
  • Search — federated search and reports
  • Pass — passport account and SSO
  • Corpora — read-only corpus origins
  • e01 — self-hosted corpora and tools

Text and metadata only; each target carries its own sources. Missing data is published as no-data, never estimated.